46 C.F.R. § 111.15-25

Current through May 31, 2024
Section 111.15-25 - Overload and reverse current protection
(a) An overload protective device must be in each battery conductor, except conductors of engine cranking batteries and batteries with a nominal potential of 6 volts or less. For large storage battery installations, the overcurrent protective devices must be next to, but outside of, the battery room.
(b) Except when a converter is used, the charging equipment for all batteries with a nominal voltage more than 20 percent of line voltage must protect automatically against reversal of current.

46 C.F.R. §111.15-25

CGD 74-125A, 47 FR 15236, Apr. 8, 1982, as amended by USCG-2020-0075, 88 FR 16361, Mar. 16, 2023
88 FR 16361, 4/17/2023