46 C.F.R. § 111.103-7

Current through May 31, 2024
Section 111.103-7 - Ventilation stop stations

Each power ventilation system stop station must:

(a) Be protected by an enclosure with a glass-paneled door on the front;
(b) Be marked, "In Case of Fire Break Glass and Operate Switch to Stop Ventilation;"
(c) Have the "stop" position of the switch clearly identified;
(d) Have a nameplate that identifies the system controlled; and
(e) Be arranged so that damage to the switch or cable automatically stops the equipment controlled.

46 C.F.R. §111.103-7

CGD 74-125A, 47 FR 15236, Apr. 8, 1982, as amended by USCG-2020-0075, 88 FR 16365, Mar. 16, 2023
88 FR 16365, 4/17/2023