46 C.F.R. § 108.445

Current through May 31, 2024
Section 108.445 - Alarm and means of escape
(a) Each CO2 system that has a supply of more than 136 kilograms (300 pounds) of CO2 , except a system that protects a tank, must have an alarm that sounds for at least 20 seconds before the CO2 is released into the space.
(b) Each audible alarm for a CO2 system must have the CO2 supply for the system as its source of power and must be in a visible location in the spaces protected.

46 C.F.R. § 108.445