46 C.F.R. § 108.439

Current through May 31, 2024
Section 108.439 - Quantity of CO[2] for protection of spaces
(a) The number of pounds of CO2 required to protect a space must be equal to the gross volume of the space divided by the appropriate factor from Table 108.439.
(b) If a machinery space includes a casing, the gross volume of the space may be calculated using the reductions allowed in 46 CFR 95.10- 5(e) .
(c) If fuel can drain from a space to an adjacent space or if two spaces are not entirely separate, the requirements for both spaces must be used to determine the amount of CO2 to be provided and the CO2 system must be arranged to discharge into both spaces simultaneously.

Table 108.439-CO2Supply Factors

[Gross volume of space in cubic feet]

OverNot over Factor
050015
5001,60016
1,6004,50018
4,50050,00020
50,00022

46 C.F.R. §108.439