= 0.98drV/dL
where:
VL = maximum volume to which tank may be loaded.
V = volume of tank.
dr = density of cargo at the temperature required for a cargo vapor pressure equal to the relief valve setting.
dL = density of cargo at the loading temperature and pressure.
Table 38.15-1(b)-Maximum Permissible Filling Densities for Tanks Operating At or Near Ambient Temperature
Specific gravity at 60 °F. | Maximum permitted filling density | ||
Unlagged tanks-water capacity | Lagged tanks-all capacities | ||
1,200 gal. and under | Over 1,200 gal. | ||
0.473-0.480 | 38 | 41 | 42 |
0.481-0.488 | 39 | 42 | 43 |
0.489-0.495 | 40 | 43 | 44 |
0.496-0.503 | 41 | 44 | 45 |
0.504-0.510 | 42 | 45 | 46 |
0.511-0.519 | 43 | 46 | 47 |
0.520-0.527 | 44 | 47 | 48 |
0.528-0.536 | 45 | 48 | 49 |
0.537-0.544 | 46 | 49 | 50 |
0.545-0.552 | 47 | 50 | 51 |
0.553-0.560 | 48 | 51 | 52 |
0.561-0.568 | 49 | 52 | 53 |
0.569-0.576 | 50 | 53 | 54 |
0.577-0.584 | 51 | 54 | 55 |
0.585-0.592 | 52 | 55 | 56 |
0.593-0.600 | 53 | 56 | 57 |
0.601-0.608 | 54 | 57 | 58 |
0.609-0.617 | 55 | 58 | 59 |
0.618-0.626 | 56 | 59 | 60 |
0.627-0.634 | 57 | 60 | 61 |
46 C.F.R. §38.15-1
Increase in filling densities to provide for seasonal changes may be considered by the Commandant upon presentation of factual evidence that safe operation can be effected.