The following non-totally enclosed PCB activities are authorized pursuant to section 6(e)(2)(B) of TSCA:
If test results show the PCB concentration (ppm) in the transformer prior to retrofill is . . . | and you retrofill the transformer with dielectric fluid containing . . . | and you . . . | and test results show the PCB concentration (ppm) after retrofill is . . . | then the transformer's reclassified status is. . . |
[GREATER THAN EQUAL TO]1,000 (or untested) | < 50 ppm PCBs | operate the transformer electrically under loaded conditions for at least 90-continuous days after retrofill, then test the fluid for PCBs | [GREATER THAN EQUAL TO]50 but < 500 | PCB-contaminated |
< 50 ppm PCBs | operate the transformer electrically under loaded conditions for at least 90-continuous days after retrofill, then test the fluid for PCBs | <50 | non-PCB | |
[GREATER THAN EQUAL TO]500 but <1,000 | <50 ppm PCBs | test the fluid for PCBs at least 90 days after retrofill | [GREATER THAN EQUAL TO]50 but <500 | PCB-contaminated |
<50 ppm PCBs | test the fluid for PCBs at least 90 days after retrofill | <50 | non-PCB | |
[GREATER THAN EQUAL TO]50 but <500 | [GREATER THAN EQUAL TO]2 but <50 ppm PCBs | test the fluid for PCBs at least 90 days after retrofill | <50 | non-PCB |
<2 ppm PCBs | (no need to test) | (not applicable) | non-PCB |
If test results show the PCB concentration (ppm) in the equipment prior to retrofill is . . . | and you retrofill the equipment with dielectric fluid containing . . . | and you . . . | and test results show the PCB concentration (ppm) after retrofill is . . . | then the electromagnet, switch, or voltage regulator's reclassified status is . . . |
[GREATER THAN EQUAL TO]1,000 (or untested) | <50 ppm PCBs | operate the equipment electrically under loaded conditions for at least 90-continuous days after retrofill, then test the fluid for PCBs | [GREATER THAN EQUAL TO]50 but <500 | PCB-contaminated |
<50 ppm PCBs | operate the equipment electrically under loaded conditions for at least 90-continuous days after retrofill, then test the fluid for PCBs | <50 | non-PCB | |
[GREATER THAN EQUAL TO]500 but <1,000 | <50 ppm PCBs | test the fluid for PCBs at least 90 days after retrofill | [GREATER THAN EQUAL TO]50 but <500 | PCB-contaminated |
<50 ppm PCBs | test the fluid for PCBs at least 90 days after retrofill | <50 | non-PCB | |
[GREATER THAN EQUAL TO]50 but <500 | [GREATER THAN EQUAL TO]2 but <50 ppm PCBs | test the fluid for PCBs at least 90 days after retrofill | <50 | non-PCB |
<2 ppm PCBs | (no need to test) | (not applicable) | non-PCB |
40 C.F.R. §761.30
Sec. 6 , Pub. L. 94-469 , 90 Stat. 2020, 2025 (15 U.S.C. 2605
For Federal Register citations affecting §761.30 see the List of CFR Sections Affected, which appears in the Finding Aids section of the printed volume and at www.fdsys.gov.