Routine Monitoring Frequency for TTHM and HAA5
Type of system | Minimum monitoring frequency | Sample location in the distribution system |
Subpart H system serving at least 10,000 persons | Four water samples per quarter per treatment plant | At least 25 percent of all samples collected each quarter at locations representing maximum residence time. Remaining samples taken at locations representative of at least average residence time in the distribution system and representing the entire distribution system, taking into account number of persons served, different sources of water, and different treatment methods.1 |
Subpart H system serving from 500 to 9,999 persons | One water sample per quarter per treatment plant | Locations representing maximum residence time.1 |
Subpart H system serving fewer than 500 persons | One sample per year per treatment plant during month of warmest water temperature. | Locations representing maximum residence time.1 If the sample (or average of annual samples, if more than one sample is taken) exceeds the MCL, the system must increase monitoring to one sample per treatment plant per quarter, taken at a point reflecting the maximum residence time in the distribution system, until the system meets criteria in paragraph (b)(1)(iv) of this section. |
System using only ground water not under direct influence of surface water using chemical disinfectant and serving at least 10,000 persons | One water sample per quarter per treatment plant2 | Locations representing maximum residence time.1 |
System using only ground water not under direct influence of surface water using chemical disinfectant and serving fewer than 10,000 persons | One sample per year per treatment plant2 during month of warmest water temperature. | Locations representing maximum residence time.1 If the sample (or average of annual samples, if more than one sample is taken) exceeds the MCL, the system must increase monitoring to one sample per treatment plant per quarter, taken at a point reflecting the maximum residence time in the distribution system, until the system meets criteria in paragraph (b)(1)(iv) of this section. |
1 If a system elects to sample more frequently than the minimum required, at least 25 percent of all samples collected each quarter (including those taken in excess of the required frequency) must be taken at locations that represent the maximum residence time of the water in the distribution system. The remaining samples must be taken at locations representative of at least average residence time in the distribution system.
2 Multiple wells drawing water from a single aquifer may be considered one treatment plant for determining the minimum number of samples required, with State approval in accordance with criteria developed under § 142.16(h)(5) of this chapter.
Reduced Monitoring Frequency for TTHM and HAA5
If you are a . . . | You may reduce monitoring if you have monitored at least one year and your . . . | To this level |
Subpart H system serving at least 10,000 persons which has a source water annual average TOC level, before any treatment, [LESS THAN EQUAL TO]4.0 mg/L | TTHM annual average [LESS THAN EQUAL TO]0.040 mg/L and HAA5 annual average [LESS THAN EQUAL TO]0.030 mg/L | One sample per treatment plant per quarter at distribution system location reflecting maximum residence time. |
Subpart H system serving from 500 to 9,999 persons which has a source water annual average TOC level, before any treatment, [LESS THAN EQUAL TO]4.0 mg/L | TTHM annual average [LESS THAN EQUAL TO]0.040 mg/L and HAA5 annual average [LESS THAN EQUAL TO]0.030 mg/L | One sample per treatment plant per year at distribution system location reflecting maximum residence time during month of warmest water temperature. NOTE: Any Subpart H system serving fewer than 500 persons may not reduce its monitoring to less than one sample per treatment plant per year. |
System using only ground water not under direct influence of surface water using chemical disinfectant and serving at least 10,000 persons | TTHM annual average [LESS THAN EQUAL TO]0.040 mg/L and HAA5 annual average [LESS THAN EQUAL TO]0.030 mg/L | One sample per treatment plant per year at distribution system location reflecting maximum residence time during month of warmest water temperature |
System using only ground water not under direct influence of surface water using chemical disinfectant and serving fewer than 10,000 persons | TTHM annual average [LESS THAN EQUAL TO]0.040 mg/L and HAA5 annual average [LESS THAN EQUAL TO]0.030 mg/L for two consecutive years OR TTHM annual average [LESS THAN EQUAL TO]0.020 mg/L and HAA5 annual average [LESS THAN EQUAL TO]0.015 mg/L for one year | One sample per treatment plant per three year monitoring cycle at distribution system location reflecting maximum residence time during month of warmest water temperature, with the three-year cycle beginning on January 1 following quarter in which system qualifies for reduced monitoring. |
40 C.F.R. §141.132