40 C.F.R. § 63.1662-63 app Table 1 to Subpart JJJJJJ of Part 63

Current through May 31, 2024
Appendix Table 1 to Subpart JJJJJJ of Part 63 - Emission Limits

As stated in § 63.11201 , you must comply with the following applicable emission limits:

If your boiler is in this subcategory . . .For the following
pollutants . . .
You must achieve less than or equal to the following emission limits, except during periods of startup and shutdown . . .
1. New coal-fired boilers with heat input capacity of 30 million British thermal units per hour (MMBtu/hr) or greater that do not meet the definition of limited-use boilera. PM (Filterable)
b. Mercury
c. CO
3.0E-02 pounds(lb) per million British thermal units (MMBtu) of heat input.
2.2E-05 lb per MMBtu of heat input.
420 parts per million (ppm) by volume on a dry basis corrected to 3 percent oxygen (3-run average or 10-day rolling average).
2. New coal-fired boilers with heat input capacity of between 10 and 30 MMBtu/hr that do not meet the definition of limited-use boilera. PM (Filterable)
b. Mercury
c. CO
4.2E-01 lb per MMBtu of heat input.
2.2E-05 lb per MMBtu of heat input.
420 ppm by volume on a dry basis corrected to 3 percent oxygen (3-run average or 10-day rolling average).
3. New biomass-fired boilers with heat input capacity of 30 MMBtu/hr or greater that do not meet the definition of seasonal boiler or limited-use boilerPM (Filterable)3.0E-02 lb per MMBtu of heat input.
4. New biomass fired boilers with heat input capacity of between 10 and 30 MMBtu/hr that do not meet the definition of seasonal boiler or limited-use boilerPM (Filterable)7.0E-02 lb per MMBtu of heat input.
5. New oil-fired boilers with heat input capacity of 10 MMBtu/hr or greater that do not meet the definition of seasonal boiler or limited-use boilerPM (Filterable)3.0E-02 lb per MMBtu of heat input.
6. Existing coal-fired boilers with heat input capacity of 10 MMBtu/hr or greater that do not meet the definition of limited-use boilera. Mercury
b. CO
2.2E-05 lb per MMBtu of heat input.
420 ppm by volume on a dry basis corrected to 3 percent oxygen (3-run average or 10-day rolling average).

40 C.F.R. 63.1662-63 app Table 1 to Subpart JJJJJJ of Part 63

78 FR 7517, Feb. 1, 2013, as amended at 81 FR 63130, Sept. 14, 2016
As amended at 81 FR 63129, 9/14/2016