Current through November 30, 2024
Section 62.14442 - What must my inspection include?(a) At a minimum, you must do the following during your HMIWI equipment inspection: (1) Inspect all burners, pilot assemblies, and pilot sensing devices for proper operation, and clean pilot flame sensor as necessary;(2) Check for proper adjustment of primary and secondary chamber combustion air, and adjust as necessary;(3) Inspect hinges and door latches, and lubricate as necessary;(4) Inspect dampers, fans, and blowers for proper operation;(5) Inspect HMIWI door and door gaskets for proper sealing;(6) Inspect motors for proper operation;(7) Inspect primary chamber refractory lining, and clean and repair/replace lining as necessary;(8) Inspect incinerator shell for corrosion and/or hot spots;(9) Inspect secondary/tertiary chamber and stack, and clean as necessary;(10) Inspect mechanical loader, including limit switches, for proper operation, if applicable;(11) Visually inspect waste bed (grates), and repair/ seal, as necessary;(12) For the burn cycle that follows the inspection, document that the incinerator is operating properly and make any necessary adjustments;(13) Inspect air pollution control device(s) for proper operation, if applicable;(14) Inspect waste heat boiler systems to ensure proper operation, if applicable;(15) Inspect bypass stack components;(16) Ensure proper calibration of thermocouples, sorbent feed systems and any other monitoring equipment; and(17) Include inspection elements according to manufacturer's recommendations; and(18) Generally observe that the equipment is maintained in good operating condition.(b) At a minimum, you must do the following during your air pollution control device inspection: (1) Inspect air pollution control device(s) for proper operation, if applicable;(2) Ensure proper calibration of thermocouples, sorbent feed systems and any other monitoring equipment; and(3) Include inspection elements according to manufacturer's recommendations; and(4) Generally observe that the equipment is maintained in good operating condition. 65 FR 49881 , Aug. 15, 2000, as amended at 78 FR 28068 , May 13, 2013