If you choose to install a subsea water injection system, your system must comply with your approved DWOP, which must meet the following minimum requirements:
Valve | Allowable leakage rate | Testing frequency |
(i) WISDV | Zero leakage | Monthly, not to exceed 6 weeks between tests. |
(ii) Surface-controlled SSSV or WIV | 400 cc per minute of liquid or 15 scf per minute of gas | Semiannually, not to exceed 6 calendar months between tests. |
30 C.F.R. §250.874