30 C.F.R. § 57.22306

Current through May 31, 2024
Section 57.22306 - Methane monitors (I-A mines)
(a) Methane monitors shall be installed on continuous mining machines, longwall mining systems, and on loading and haulage equipment used in or beyond the last open crosscut.
(b) The monitors shall-
(1) Give warning at 1.0 percent methane;
(2) Automatically deenergize electrical equipment, except power to monitoring equipment determined by MSHA to be intrinsically safe under 30 CFR part 18 , and prevent starting such equipment when methane levels reach 1.5 percent. Diesel equipment shall be shut off or immediately removed from the affected area; and
(3) Automatically deenergize electrical equipment when power to a sensor is interrupted. Diesel equipment shall not be operated if the monitor is inoperative.
(c) Sensing units of monitors shall be positioned at a location which provides for the most effective measurement of methane.

30 C.F.R. §57.22306