30 C.F.R. § 18 app I to Subpart D of Part 18

Current through May 31, 2024
Appendix I to Subpart D of Part 18 - Appendix I to Subpart D of Part 18

LIST OF TABLES

Table No. Title
1Portable power cable ampacities-600 volts.
2Portable cord ampacities-600 volts.
3Portable power cable ampacities-601 to 5,000 volts.
4Normal diameter of round cables with tolerances in inches-600 volts.
5Nominal dimension of flat cables with tolerances in inches-600 volts.
6Nominal diameter of heavy jacketed cords with tolerances in inches-600 volts.
7Nominal diameter of three-conductor portable power cables with tolerances in inches-601 to 5,000 volts.
8Fuse ratings or instantaneous settings of circuit breakers for short-circuit protection of portable cables.
9Specifications for portable cables longer than 500 feet.
10High voltage trailing cable ampacities and outside diameters.

Table 1-Portable Power Cable Ampacities-600 Volts (Amperes Per Conductor Based on 60 °C. Copper Temperature-40 °C. Ambient)

Conductor size-AWG or MCMSingle conductor2-conductor, round or flat3-conductor, round or flat4-conductor5-conductor6-conductor
8454035302520
6605050403530
4857065554535
3958075655545
21109590756555
1130110100857565
1/01501301201009080
2/017515013511510595
3/0205175155130120110
4/0235200180150140130
250275220200160
300305240220175
350345240235190
400375280250200
450400300270215
500425320290230

Table 2-Portable Cord Ampacities-600 Volts (Amperes Per Conductor Based on 60 °C. Copper Temperature-40 °C. Ambient)

Conductor size-AWG1-3 conductor4-6 conductor7-9 conductor
1415128
12201611
10252014

Table 3-Portable Power Cable Ampacities-601 to 5,000 Volts (Amperes Per Conductor Based on 75 °C. Copper Temperature-40 °C. Ambient)

Conductor size-AWG or MCM 3-conductor types G-GC and SIIC-GC 2,000 volts 3-conductor type SHD-GC 2,001-5,000 volts
66565
48585
3100100
2115115
1130130
1/0145145
2/0170170
3/0195195
4/0220220
250245245
300275275
350305305

Table 4-Nominal Diameters of Round Cables With Tolerances in Inches-600 Volts

Conductor size-AWG or MCMSingle conductor2-conductor3-conductor4-conductor-Types W & G5-conductor-Types W & G6-conductor
Types W & G twistedType PG, 2 powerType PCG, 3 power, groundTypes W & GType PG, 3 power, groundType PCG, 3 power, 2 control, groundType wTolerance
80.440.810.840.940.910.931.030.991.071.18±0.03
6.51.93.93.981.011.031.181.101.211.31±.03
4.571.081.081.101.171.201.291.271.401.52±.03
3.631.171.171.201.241.271.311.341.481.61±.03
2.661.271.271.291.341.341.391.481.611.75±.03
1.741.441.441.441.511.521.521.681.882.05±.03
1/0.771.521.521.521.651.681.681.791.962.13±.04
2/0.821.651.651.651.751.791.791.932.132.32±.04
3/0.871.771.771.771.891.931.932.072.262.49±.05
4/0.931.921.921.922.042.132.132.262.462.71±.05
2501.032.162.162.162.392.392.392.66±.06
3001.092.322.562.84±.06
3501.152.432.682.98±.06
4001.202.572.823.14±.06
4501.262.672.943.26±.06
5001.312.763.033.40±.06

Table 5-Nominal Dimensions of Flat Cables With Tolerances in Inches-600 Volts

Conductor size-AWG2-conductor3-conductor-Type G
Type WType GMajorMinor
MajorMinorMajorMinorO.D.ToleranceO.D.Tolerance
O.D.ToleranceO.D.ToleranceO.D.ToleranceO.D.Tolerance
80.84±0.040.51±0.03
6.93±.04.56±.031.02±.040.56±.031.65±0.060.67±0.05
41.05±.04.61±.031.15±.04.61±.031.85±.06.75±.05
31.14±.04.68±.031.26±.04.68±.031.99±.06.77±.05
21.24±.04.73±.031.35±.04.73±.062.10±.06.81±.05
11.40±.04.81±.031.55±.04.81±.032.43±.06.97±.05
1/01.51±.04.93±.031.67±.04.93±.03
2/01.63±.04.99±.031.85±.04.99±.03
3/01.77±.041.03±.032.00±.041.03±.03
4/01.89±.041.10±.032.10±.041.10±.03

Table 6-Nominal Diameters of Heavy Jacketed Cords With Tolerances In Inches-600 Volts

Conductor size-AWG2-conductor3-conductor4-conductor5-conductor6-conductor7-conductor
DiameterToleranceDiameterToleranceDiameterToleranceDiameterToleranceDiameterToleranceDiameterTolerance
140.64±0.020.67±0.020.71±0.020.78±0.030.83±0.030.89±0.03
12.68±.02.72±.03.76±.03.83±.03.89±.03.98±.03
10.73±.03.80±.03.84±.03.90±.031.00±.031.07±.03

Table 7-Nominal Diameters of Three-Conductor Portable Power Cables With Tolerances in Inches-601 to 5,000 Volts

Conductor size-AWG or MCMType G-GC (nonshielded) 2,000 voltsType SHC-GC (shielded overall) 2,000 voltsType SHD-GC (individually shielded power conductors) 2,001-3,000 voltsType SHD-GC (individually shielded power conductors) 3,001-5,000 volts
DiameterToleranceDiameterToleranceDiameterToleranceDiameterTolerance
61.25+ 0.10, -0.061.39+ 0.11, -0.071.62+ 0.13, -0.081.78+ 0.14, -0.09
41.40+ .11, -.071.55+ .12, -.081.77+ .14, -.091.90+ .15, -.10
31.48+ .12, -.071.62+ .13, -.081.84+ .15, -.091.98+ .16, -.10
21.55+ .12, -.081.71+ .14, -.091.92+ .15, -.102.09+ .17, -.11
11.74+ .14, -.091.89+ .15, -.092.04+ .16, -.102.18+ .17, -.11
1/01.84+ .15, -.092.02+ .16, -.102.18+ .17, -.112.34+ .19, -.12
2/01.99+ .16, -.102.16+ .17, -.112.29+ .18, -.122.46+ .20, -.12
3/02.12+ .17, -.112.30+ .18, -.112.45+ .20, -.122.62+ .21, -.13
4/02.30+ .18, -.122.48+ .20, -.122.62+ .21, -.132.76+ .22, -.14
2502.46+ .20, -.122.70+ .22, -.13
3002.63+ .21, -.132.84+ .23, -.14
3502.75+ .22, -.142.97+ .24, -.15

Table 8-Fuse Ratings or Instantaneous Setting of Circuit Breakers for Short-Circuit Protection of Portable Cables and Cords

Conductor size-AWG or MCM Ohms/1,000 ft. at 25 °C. Maximum allowable fuse rating (amperes) Maximum allowable circuit breaker instantaneous setting (amperes)1
142.622050
121.653075
101.0440150
8.65480200
6.410100300
4.259200500
3.205250600
2.162300800
1.1293751,000
1/0.1025001,250
2/0.0811,500
3/0.0642,000
4/0.0512,500
250.0432,500
300.0362,500
350.0312,500
400.0272,500
450.0242,500
500.0222,500

1 Higher circuit-breaker settings may be permitted for special applications when justified.

Table 9-Specifications for Portable Cables Longer Than 500 Feet1

Conductor size-AWG or MCMMax. allowable length (feet) Normal ampacity at 60 °C. copper temperature (40 °C. ambient) Resistance at 60 °C. copper temperature (ohms)
6550500.512
460070.353
365080.302
270095.258
1750110.220
1/0800130.185
2/0850150.157
3/0900175.130
4/01,000200.116
2501,000220.098
3001,000240.082
3501,000260.070
4001,000280.061
4501,000300.054
5001,000320.050

1 Fuses shall not be used for short-circuit protection of these cables. Circuit breakers shall be used with the instantaneous trip settings not to exceed the values given in Table 8.

Table 10-High Voltage Trailing Cable Ampacities and Outside Diameters

Power conductor Ampacity *Outside diameter **
(inches)
Size AWG or kcmil Amperes per conductor SHD-GC 2001 to 5000 volts SHD-CGC 2001 to 5000 volts SHD-PCG 2001 to 5000 volts
6931.561.62
41221.681.73
31401.781.821.94
21591.871.912.03
11841.951.982.12
1/02112.082.102.26
2/02432.202.202.40
3/02792.362.362.58
4/03212.502.502.76
2503552.692.69
3003982.812.81
3504352.952.95
5005363.313.31

* These ampacities are based on single isolated conductor in air, operated with open-circuited shield for a 90 °C conductor temperature and an ambient temperature of 40 °C.

** Tolerances for the outside diameter are + 8%/-5%.

30 C.F.R. 18 app I to Subpart D of Part 18

33 FR 4660, Mar. 19, 1968; 33 FR 6345, Apr. 26, 1968, as amended at 42 FR 8373, Feb. 10, 1977; 75 FR 17549, Apr. 6, 2010; 75 FR 20918, Apr. 22, 2010