Table F-2
Fire protection provided | Fire resistance | Maximum size | Total allowable quantities gals./sq. ft./floor area |
Yes | 2 hrs | 500 sq. ft | 10 |
No | 2 hrs | 500 sq. ft | 4 |
Yes | 1 hr | 150 sq. ft | 5 |
No | 1 hr | 150 sq. ft | 2 |
NOTE: Fire protection system shall be sprinkler, water spray, carbon dioxide or other system approved by a nationally recognized testing laboratory for this purpose.
This paragraph may be used for operating pressures not exceeding 1 p.s.i.g.
Exemption: Tanks of 3,000 bbls (barrels) (84 m(3)) capacity or less containing crude petroleum in crude-producing areas; and, outside aboveground atmospheric tanks under 1,000 gallons (3,785 L) capacity containing other than Category 1 flammable liquids may have open vents. (See paragraph (i)(2)(vi)(B) of this section.)
Table F-10-Wetted Area Versus Cubic Feet (Meters) Free Air Per Hour
[14.7 psia and 60 °F. (15.55 °C)]
Square feet (m2) | CFH (m3H) | Square feet (m2) | CFH (m3H) | Square feet (m2) | CFH (m3H) |
20 (1.84) | 21,100 (590.8) | 200 (18.4) | 211,000 (5,908) | 1,000 (90.2) | 524,000 (14,672) |
30 (2.76) | 31,600 (884.8) | 250 (23) | 239,000 (6,692) | 1,200 (110.4) | 557,000 (15,596) |
40 (3.68) | 42,100 (1,178.8) | 300 (27.6) | 265,000 (7,420) | 1,400 (128.8) | 587,000 (16,436) |
50 (4.6) | 52,700 (1,475.6) | 350 (32.2) | 288,000 (8,064) | 1,600 (147.2) | 614,000 (17,192) |
60 (5.52) | 63,200 (1,769.6) | 400 (36.8) | 312,000 (8,736) | 1,800 (165.6) | 639,000 (17,892) |
70 (6.44) | 73,700 (2,063.6) | 500 (46) | 354,000 (9,912) | 2,000 (180.4) | 662,000 (18,536) |
80 (7.36) | 84,200 (2,357.6) | 600 (55.2) | 392,000 (10,976) | 2,400 (220.8) | 704,000 (19,712) |
90 (8.28) | 94,800 (2,654.4) | 700 (64.4) | 428,000 (11,984) | 2,800 (257.6) | 742,000 (20,776) |
100 (9.2) | 105,000 (2,940) | 800 (73.6) | 462,000 (12,936) | and | |
120 (11.04) | 126,000 (3,528) | 900 (82.8) | 493,000 (13,804) | over | |
140 (12.88) | 147,000 (4,116) | 1,000 (90.2) | 524,000 (14,672) | ||
160 (14.72) | 168,000 (4,704) | ||||
180 (16.56) | 190,000 (5,320) | ||||
200 (18.4) | 211,000 (5,908) |
CFH = 1,107A0.82
Where:
CFH = Venting requirement, in cubic feet (meters) of free air per hour.
A = Exposed wetted surface, in square feet (m2).
Note: The foregoing formula is based on Q = 21,000A0.82.
V = 1337 ÷L[RADIC]M
V = Cubic feet (meters) of free air per hour from Table F-10.
L = Latent heat of vaporization of specific liquid in B.t.u. per pound.
M = Molecular weight of specific liquids.
0.5 for drainage in accordance with paragraph (i)(2)(vii)(B) of this section for tanks over 200 square feet (18.4 m2) of wetted area.
0.3 for approved water spray.
0.3 for approved insulation.
0.15 for approved water spray with approved insulation.
Table F-11-Vent Line Diameters
Maximum flow GPM (L) | Pipe length1 | ||
50 feet (15.2 m) | 100 feet (30.4 m) | 200 feet (60.8 m) | |
Inches (cm) | Inches (cm) | Inches (cm) | |
100 (378.5) | 11/4 (3.175) | 11/4 (3.175) | 11/4 (3.175) |
200 (757) | 11/4 (3.175) | 11/4 (3.175) | 11/4 (3.175) |
300 (1,135.5) | 11/4 (3.175) | 11/4 (3.175) | 11/2 (3.81) |
400 (1,514) | 11/4 (3.175) | 11/2 (3.81) | 2 (5.08) |
500 (1,892.5) | 11/2 (3.81) | 11/2 (3.81) | 2 (5.08) |
600 (2,271) | 11/2 (3.81) | 2 (5.08) | 2 (5.08) |
700 (2,649.5) | 2 (5.08) | 2 (5.08) | 2 (5.08) |
800 (3,028) | 2 (5.08) | 2 (5.08) | 3 (7.62) |
900 (3,406.5) | 2 (5.08) | 2 (5.08) | 3 (7.62) |
1,000 (3,785) | 2 (5.08) | 2 (5.08) | 3 (7.62) |
1 Vent lines of 50 ft. (15.2 m), 100 ft. (30.4 m), and 200 ft. (60.8 m) of pipe plus 7 ells.
29 C.F.R. §1926.152