Table 1 to § 3285.303 -Frame Blocking Only/Perimeter Support Not Required Except at Openings
Pier spacing | Roof live load (psf) | Location | Load (lbs.) |
20 | Frame | 2,900 | |
4 ft. 0 in. | 30 | Frame | 3,300 |
40 | Frame | 3,600 | |
20 | Frame | 4,200 | |
6 ft. 0 in. | 30 | Frame | 4,700 |
40 | Frame | 5,200 | |
20 | Frame | 5,500 | |
8 ft. 0 in. | 30 | Frame | 6,200 |
40 | Frame | 6,900 | |
20 | Frame | 6,800 | |
10 ft. 0 in. | 30 | Frame | 7,600 |
40 | Frame | 8,500 |
Notes:
Table 2 to § 3285.303 -Frame Plus Perimeter Blocking/Perimeter Blocking Required
Maximum pier spacing | Roof live load(psf) | Location | Load (lbs.) |
Frame | 1,400 | ||
4 ft. 0 in. | 20 | Perimeter | 1,900 |
Mating | 3,200 | ||
Frame | 1,400 | ||
4 ft. 0 in. | 30 | Perimeter | 2,300 |
Mating | 3,800 | ||
Frame | 1,400 | ||
4 ft. 0 in. | 40 | Perimeter | 2,600 |
Mating | 4,400 | ||
Frame | 1,900 | ||
6 ft. 0 in. | 20 | Perimeter | 2,700 |
Mating | 4,700 | ||
Frame | 1,900 | ||
6 ft. 0 in. | 30 | Perimeter | 3,200 |
Mating | 5,600 | ||
Frame | 1,900 | ||
6 ft. 0 in. | 40 | Perimeter | 3,700 |
Mating | 6,500 | ||
Frame | 2,400 | ||
8 ft. 0 in. | 20 | Perimeter | 3,500 |
Mating | 6,100 | ||
Frame | 2,400 | ||
8 ft. 0 in. | 30 | Perimeter | 4,200 |
Mating | 7,300 | ||
Frame | 2,400 | ||
8 ft. 0 in. | 40 | Perimeter | 4,800 |
Mating | 8,500 | ||
Frame | 2,900 | ||
10 ft. 0 in. | 20 | Perimeter | 4,300 |
Mating | 7,600 | ||
Frame | 2,900 | ||
10 ft. 0 in. | 30 | Perimeter | 5,100 |
Mating | 9,100 | ||
Frame | 2,900 | ||
10 ft. 0 in. | 40 | Perimeter | 6,000 |
Mating | 10,600 |
Notes:
Table 3 to § 3285.303 -Ridge Beam Span Footing Capacity
Mating wall opening (ft) | Roof live load (psf) | Pier and footing load (lbs.) |
20 | 1,200 | |
5 | 30 | 1,600 |
40 | 1,900 | |
20 | 2,300 | |
10 | 30 | 3,100 |
40 | 3,800 | |
20 | 3,500 | |
15 | 30 | 4,700 |
40 | 5,800 | |
20 | 4,700 | |
20 | 30 | 6,200 |
40 | 7,500 | |
20 | 5,800 | |
25 | 30 | 7,800 |
40 | 9,700 | |
20 | 7,000 | |
30 | 30 | 9,300 |
40 | 11,600 | |
20 | 8,100 | |
35 | 30 | 10,900 |
40 | 13,600 |
Notes:
1. See Table to § 3285.312 for cast-in-place footing design by using the noted loads.
2. Table 3 is based on the following design assumptions: maximum 16 ft. nominal section width (15 ft. actual width), 10" I-beam size, 300 lbs. pier dead load, 10 psf roof dead load, 6 psf floor dead load, 35 plf wall dead load, and 10 plf chassis dead load.
3. Loads listed are maximum column loads for each section of the manufactured home.
4. Interpolation for maximum allowable pier and column loads is permitted for mate-line openings between those shown in the table.
5. The pier spacing and loads shown in the above table do not consider flood or seismic loads and are not intended for use in flood or seismic hazard areas. In those areas, the foundation support system must be designed by a professional engineer or registered architect.
6. See Table to § 3285.312 for sizing of footings.
24 C.F.R. §3285.303