Table to paragraph (d)-Maximum Capacity of Different Sizes of Pipe and Tubing in Thousands of Btu/hr of Natural Gas for Gas Pressures of 0.5 psig or Less, and a Maximum Pressure Drop of 1/2 in. Water Column
ID (in.) | 10 ft | 20 ft | 30 ft | 40 ft | 50 ft | 60 ft | 70 ft | 80 ft | 90 ft | 100 ft |
Iron Pipe Sizes-Length | ||||||||||
1/4 | 43 | 29 | 24 | 20 | 18 | 16 | 15 | 14 | 13 | 12 |
3/8 | 95 | 65 | 52 | 45 | 40 | 36 | 33 | 31 | 29 | 27 |
1/2 | 175 | 120 | 97 | 82 | 73 | 66 | 61 | 57 | 53 | 50 |
3/4 | 360 | 250 | 200 | 170 | 151 | 138 | 125 | 118 | 110 | 103 |
1 | 680 | 465 | 375 | 320 | 285 | 260 | 240 | 220 | 215 | 195 |
EHD2 | ID (in.) | 10 ft | 20 ft | 30 ft | 40 ft | 50 ft | 60 ft | 70 ft | 80 ft | 90 ft | 100 ft |
Corrugated Stainless Steel Tubing-Length1 | |||||||||||
13 | 3/8 | 31 | 21 | 17 | 14 | 13 | 12 | 11 | 10 | 10 | 9 |
15 | 3/8 | 42 | 30 | 24 | 20 | 18 | 16 | 15 | 14 | 13 | 12 |
18 | 1/2 | 79 | 56 | 45 | 39 | 36 | 33 | 30 | 28 | 27 | 25 |
19 | 1/2 | 91 | 64 | 52 | 45 | 40 | 36 | 35 | 32 | 31 | 29 |
23 | 3/4 | 155 | 111 | 92 | 80 | 72 | 65 | 60 | 58 | 55 | 52 |
25 | 3/4 | 184 | 132 | 108 | 93 | 84 | 77 | 71 | 66 | 62 | 60 |
30 | 1 | 317 | 222 | 180 | 156 | 138 | 126 | 116 | 108 | 103 | 97 |
31 | 1 | 368 | 258 | 209 | 180 | 161 | 147 | 135 | 127 | 120 | 113 |
37 | 11/4 | 598 | 426 | 350 | 304 | 273 | 250 | 231 | 217 | 205 | 195 |
OD (in.) | 10 ft | 20 ft | 30 ft | 40 ft | 50 ft | 60 ft | 70 ft | 80 ft | 90 ft | 100 ft |
Copper Tubing-Length | ||||||||||
1/4 | 27 | 18 | 15 | 13 | 11 | 10 | 9 | 9 | 8 | 8 |
3/8 | 56 | 38 | 31 | 26 | 23 | 21 | 19 | 18 | 17 | 16 |
1/2 | 113 | 78 | 62 | 53 | 47 | 43 | 39 | 37 | 34 | 33 |
3/4 | 197 | 136 | 109 | 93 | 83 | 75 | 69 | 64 | 60 | 57 |
1 | 280 | 193 | 155 | 132 | 117 | 106 | 98 | 91 | 85 | 81 |
1 Includes losses for four 90-degree bends and two end fittings. Tubing runs with larger numbers of bend and/or fittings shall be increased by an equivalent length of tubing according to the following equation: L = 1.3n, where L is actual length (ft) of tubing and n is the number of additional fittings and/or bends.
2 EHD (Equivalent Hydraulic Diameter)-A measure of the hydraulic efficiency between different tubing sizes.
THIS OUTLET IS DESIGNED FOR USE WITH GAS PORTABLE APPLIANCES WHOSE TOTAL INPUT DO NOT EXCEED ______ BTUH. REPLACE PROTECTIVE COVERING OVER CONNECTOR WHEN NOT IN USE.
24 C.F.R. §3280.705