Uo adjusted = Uo standard * [1 + (0.6) (heating efficiency increase factor) + (cooling multiplier) (cooling efficiency increase factor)]
where:
Uo standard = Maximum Uo for Uo Zone required by § 3280.506(a)
Uo adjusted = Maximum Uo standard adjusted for high efficiency HVAC equipment
Heating efficiency increase factor = The increase factor in heating equipment efficiency measured by the Annual Fuel Utilization Efficiency (AFUE), or the Heating Seasonal Performance Factor (HSPF) for heat pumps, above that required by NAECA (indicated as "NAECA" in formula). The formula is heating efficiency increase factor = AFUE (HSPF) home - AFUE (or HSPF) NAECA divided by AFUE (HSPF) NAECA.
Cooling efficiency increase factor = the increase factor in the cooling equipment efficiency measured by the Seasonal Energy Efficiency Ratio (SEER) above that required by NAECA.
The formula being cooling equipment = SEER home-SEER NAECA divided by SEER NAECA.
The cooling multiplier for the Uo Zone is from the following table:
Uo zone | Cooling multiplier (Cm) |
1 | 0.60 (Florida only). |
1 | 0.20 (All other locations). |
2 | 0.07. |
3 | 0.03. |
24 C.F.R. §3280.508