16 C.F.R. § 305.20

Current through November 30, 2024
Section 305.20 - Labeling for central air conditioners, heat pumps, and furnaces
(a)Layout. All energy labels for central air conditioners, heat pumps, and furnaces (including boilers) shall use one size, similar colors, and typefaces with consistent positioning of headline, copy, and charts to maintain uniformity for immediate consumer recognition and readability. Trim size dimensions for all labels shall be as follows: width must be between 51/4 inches and 51/2 inches (13.34 cm. and 13.97 cm.); length must be between 73/8 inches (18.78 cm.) and 75/8 (19.34 cm.). Copy is to be set between 27 picas and 29 picas and copy page should be centered (right to left and top to bottom). Depth is variable but should follow closely the prototype labels appearing at the end of this part illustrating the basic layout. All positioning, spacing, type sizes, and line widths should be similar to and consistent with the prototype and sample labels in appendix L.
(b)Type style and setting. The Arial series typeface or equivalent shall be used exclusively on the label. Specific sizes and faces to be used are indicated on the prototype labels. No hyphenation should be used in setting headline or copy text. Positioning and spacing should follow the prototypes closely. Generally, text must be set flush left with two points leading except where otherwise indicated. See the prototype labels for specific directions.
(c)Colors. The basic colors of all labels covered by this section shall be process yellow or equivalent and process black. The label shall be printed full bleed process yellow. All type and graphics shall be print process black.
(d)Label type. The labels must be affixed in the form of an adhesive label, unless otherwise indicated by this section. All adhesive labels should be applied with an adhesive with an adhesion capacity sufficient to prevent their dislodgment during normal handling throughout the chain of distribution to the retailer or consumer. The paper stock for pressure-sensitive or other adhesive labels shall have a basic weight of not less than 58 pounds per 500 sheets (25"x38") or equivalent, exclusive of the release liner and adhesive. A minimum peel adhesion capacity for the adhesive of 12 ounces per square inch is suggested, but not required if the adhesive can otherwise meet the above standard.
(e)Placement.
(1) Manufacturers shall affix adhesive labels to the covered products in such a position that they are easily read by persons examining the products. The labels should be generally located on the upper-right-front corner of each product's front exterior. However, other prominent locations may be used as long as labels will not become dislodged during normal handling throughout the chain of distribution to retailers or consumers. Tops of the labels should not exceed 74 inches from the base of taller products. Labels can be displayed in the form of a flap tag adhered to the top of the appliance and bent (folded at 90°) to hang over the front, as long as this can be done with assurance that it will be readily visible. Labels for split-system central air conditioners should be affixed to the condensing unit.
(2) In addition to the requirements of paragraph (e)(1), for split-system and single-package central air conditioners, and all non-weatherized and mobile home furnaces manufactured on or after the compliance date of regional efficiency standards issued by the Department of Energy for those products in 10 CFR part 430, manufacturers shall affix labels to covered product packages or the products themselves in positions that allow persons examining the packaged products to read the labels easily. Labels on packaging must be affixed via adhesive or another means sufficient to prevent their dislodgment during normal handling throughout the chain of distribution to the retailer or consumer. Labels for split-system central air conditioners should be affixed to condensing units' packages or condensing units consistent with this paragraph.
(f)Content of furnace labels: Content of labels for non-weatherized furnaces, weatherized furnaces, mobile home furnaces, electric furnaces, and boilers.
(1) Headlines and texts, as illustrated in the prototype and sample labels in appendix L to this part.
(2) Name of manufacturer or private labeler shall, in the case of a corporation, be deemed to be satisfied only by the actual corporate name, which may be preceded or followed by the name of the particular division of the corporation. In the case of an individual, partnership, or association, the name under which the business is conducted shall be used. Inclusion of the name of the manufacturer or private labeler is optional at the discretion of the manufacturer or private labeler.
(3) The model's basic model number. The label may include multiple model numbers on a single label for models as long as the models share the same efficiency ratings and capacities and the presentation of such information is clear and prominent.
(4) The model's capacity. Inclusion of capacity is optional at the discretion of the manufacturer or private labeler.
(5) The annual fuel utilization efficiency (AFUE) for furnace models as determined in accordance with this part.
(6) Ranges of comparability consisting of the lowest and highest annual fuel utilization efficiency (AFUE) ratings for all furnaces of the model's type consistent with the sample labels in appendix L.
(7) Placement of the labeled product on the scale shall be proportionate to the lowest and highest annual fuel utilization efficiency ratings forming the scale.
(8) The following statement shall appear in bold print on furnace labels adjacent to the range(s) as illustrated in the sample labels in appendix L:

For energy cost info, visit productinfo.energy.gov.

(9) The following statement shall appear at the top of the label as illustrated in the sample labels in appendix L to this part:

Federal law prohibits removal of this label before consumer purchase.

(10) No marks or information other than that specified in this part shall appear on or directly adjoining this label except that:
(i) A part or publication number identification may be included on this label, as desired by the manufacturer. If a manufacturer elects to use a part or publication number, it must appear in the lower right-hand corner of the label and be set in 12-point type or smaller.
(ii) The energy use disclosure labels required by the governments of Canada or Mexico may appear directly adjoining this label, as desired by the manufacturer.
(iii) The manufacturer may include the ENERGY STAR logo on the label for certified products in a location consistent with the sample labels in appendix L to this part. The logo must be no larger than 1 inch by 3 inches in size. Only manufacturers that have signed a Memorandum of Understanding with the Department of Energy or the Environmental Protection Agency may add the ENERGY STAR logo to labels on qualifying covered products; such manufacturers may add the ENERGY STAR logo to labels only on those covered products that are contemplated by the Memorandum of Understanding.
(11) Manufacturers of boilers shipped with more than one input nozzle to be installed in the field must label such boilers with the AFUE of the system when it is set up with the nozzle that results in the lowest AFUE rating.
(12) Manufacturers that ship out boilers that may be set up as either steam or hot water units must label the boilers with the AFUE rating derived by conducting the required test on the boiler as a hot water unit.
(13) Manufacturers of oil furnaces must label their products with the AFUE rating associated with the furnace's input capacity set by the manufacturer at shipment. The oil furnace label may also contain a chart, as illustrated in sample label 9B in appendix L to this part, indicating the efficiency rating at up to three additional input capacities offered by the manufacturer. Consistent with paragraph (f)(10)(iii) of this section, labels for oil furnaces may include the ENERGY STAR logo only if the model qualifies for that program on all input capacities displayed on the label.
(14) Manufacturers of models that qualify as both furnaces and central air conditioners or heat pumps under DOE requirements may combine the disclosures required by this section on one label for models that meet all applicable DOE regional efficiency standards.
(g)Content of central air conditioner labels: Content of labels for central air conditioners and heat pumps.
(1) Headlines and texts, as illustrated in the prototype and sample labels in appendix L to this part.
(2) Name of manufacturer or private labeler shall, in the case of a corporation, be deemed to be satisfied only by the actual corporate name, which may be preceded or followed by the name of the particular division of the corporation. In the case of an individual, partnership, or association, the name under which the business is conducted shall be used. Inclusion of the name of the manufacturer or private labeler is optional at the discretion of the manufacturer or private labeler.
(3) The model's basic model number. The label may include multiple model numbers on a single label for models as long as the models share the same efficiency ratings and capacities and the presentation of such information is clear and prominent.
(4) The model's capacity. Inclusion of capacity is optional at the discretion of the manufacturer or private labeler for all models except split-system labels, which may not disclose capacity.
(5) The seasonal energy efficiency ratio 2 (SEER2) for the cooling function of central air conditioners as determined in accordance with this part. For the heating function, the heating seasonal performance factor 2 (HSPF2) shall be calculated for heating Region IV for the standardized design heating requirement nearest the capacity measured in the High Temperature Test in accordance with this part. In addition, as illustrated in the sample labels in appendix L to this part, the ratings for any split-system air conditioner condenser evaporator coil combinations shall be the minimum rating of all condenser-evaporator coil combinations certified to the Department of Energy pursuant to 10 CFR part 430 . The ratings for any split-system heat pump condenser-evaporator coil combinations shall include the low and high ratings of all condenser-evaporator coil combinations certified to the Department of Energy pursuant to 10 CFR part 430.
(6)
(i) Each cooling-only central air conditioner label shall contain a range of comparability consisting of the lowest and highest SEER2 for all cooling-only central air conditioners consistent with sample label 7 in appendix L to this part.
(ii) Each heat pump label, except as noted in paragraph (g)(6)(iii) of this section, shall contain two ranges of comparability. The first range shall consist of the lowest and highest seasonal energy efficiency ratios for the cooling side of all heat pumps consistent with sample label 8 in appendix L to this part. The second range shall consist of the lowest and highest heating seasonal performance factors for the heating side of all heat pumps consistent with sample label 8 in appendix L to this part.
(iii) Each heating-only heat pump label shall contain a range of comparability consisting of the lowest and highest heating seasonal performance factors for all heating-only heat pumps following the format of sample label 8 in appendix L to this part.
(7) Placement of the labeled product on the scale shall be proportionate to the lowest and highest efficiency ratings forming the scale.
(8) The following statement shall appear on the label in bold print as indicated in the sample labels in appendix L to this part.

For energy cost info, visit productinfo.energy.gov.

(9) All labels on split-system condenser units must contain one of the following three statements:
(i) For labels disclosing only the seasonal Energy Efficiency Ratio 2 for cooling, the statement should read:

* Your air conditioner's efficiency rating may be better depending on the coil your contractor installs.

(ii) For labels disclosing both the seasonal Energy Efficiency Ratio 2 for cooling and the heating seasonal performance factor 2 for heating, the statement should read:

This system's efficiency ratings depend on the coil your contractor installs with this unit. The heating efficiency rating varies slightly in different geographic regions. Ask your contractor for details.

(iii) For labels disclosing only the heating seasonal performance factor 2 for heating, the statement should read:

This system's efficiency rating depends on the coil your contractor installs with this unit. The efficiency rating varies slightly in different geographic regions. Ask your contractor for details.

(10) The following statement shall appear at the top of the label as illustrated in the sample labels in appendix L of this part:

Federal law prohibits removal of this label before consumer purchase.

(11) For any single-package air conditioner with a minimum Energy Efficiency Ratio 2 (EER2) of at least 10.6, any split system central air conditioner with a rated cooling capacity of at least 45,000 Btu/h and minimum efficiency ratings of at least 13.8 SEER2 and 11.2 EER2 or at least 15.2 SEER2 and 9.8 EER2, and any split-system central air conditioners with a rated cooling capacity less than 45,000 Btu/h and minimum efficiency ratings of at least 14.3 SEER2 and 11.7 EER2 or at least 15.2 SEER2 and 9.8 EER2, the label must contain the following regional standards information:
(i) A statement that reads:

Notice

Federal law allows this unit to be installed in all U.S. states and territories.

(ii) For split systems, a statement that reads:

Energy Efficiency Ratio 2 (EER2): The installed system's minimum EER2 is ____.

(iii) For single-package air conditioners, a statement that reads:

Energy Efficiency Ratio 2 (EER2): This model's EER2 is [____].

(12) For any split system central air conditioner with a rated cooling capacity of at least 45,000 Btu/h and minimum efficiency ratings of at least 13.8 SEER2 but lower than 11.2 EER2 or at least 15.2 SEER2 but lower than 9.8 EER2, and any split-system central air conditioners with a rated cooling capacity less than 45,000 Btu/h and minimum efficiency ratings of at least 14.3 SEER2 but lower than 11.7 EER2 or at least 15.2 SEER2 but lower than 9.8 EER2, the label must contain the following regional standards information:
(i) A statement that reads:

Notice

Federal law allows this unit to be installed only in: AK, AL, AR, CO, CT, DC, DE, FL, GA, HI, ID, IL, IA, IN, KS, KY, LA, MA, ME, MD, MI, MN, MO, MS, MT, NC, ND, NE, NH, NJ, NY, OH, OK, OR, PA, RI, SC, SD, TN, TX, UT, VA, VT, WA, WV, WI, WY and U.S. territories. Federal law prohibits installation of this unit in other states.

(ii) A map appropriate for the model and accompanying text as illustrated in the sample label 7 in appendix L of this part.
(iii) A statement that reads:

Energy Efficiency Ratio 2 (EER2): The installed system's minimum EER2 is ____.

(13) For any split system central air conditioner with a rated cooling capacity of at least 45,000 Btu/h and a minimum rated efficiency rating less than 13.8 SEER2, and any split-system central air conditioners with a rated cooling capacity less than 45,000 Btu/h and minimum efficiency ratings of less than 14.3 SEER2, the label must contain the following regional standards information:
(i) A statement that reads:

Notice

Federal law allows this unit to be installed only in: AK, CO, CT, ID, IL, IA, IN, KS, MA, ME, MI, MN, MO, MT, ND, NE, NH, NJ, NY, OH, OR, PA, RI, SD, UT, VT, WA, WV, WI, and WY. Federal law prohibits installation of this unit in other states.

(ii) A map appropriate for the model and accompanying text as illustrated in the sample label 7 in appendix L of this part.
(iii) A statement that reads:

Energy Efficiency Ratio 2 (EER2): The installed system's minimum EER2 is ____.

(14) For any single-package air conditioner with a minimum EER2 below 10.6, the label must contain the following regional standards information:
(i) A statement that reads:

Notice

Federal law allows this unit to be installed only in: AK, AL, AR, CO, CT, DC, DE, FL, GA, HI, ID, IL, IA, IN, KS, KY, LA, MA, ME, MD, MI, MN, MO, MS, MT, NC, ND, NE, NH, NJ, NY, OH, OK, OR, PA, RI, SC, SD, TN, TX, UT, VA, VT, WA, WV, WI, WY and U.S. territories. Federal law prohibits installation of this unit in other states.

(ii) A map appropriate for the model and accompanying text as illustrated in the sample label 7 in appendix L of this part.
(15) No marks or information other than that specified in this part shall appear on or directly adjoining this label except that:
(i) A part or publication number identification may be included on this label, as desired by the manufacturer. If a manufacturer elects to use a part or publication number, it must appear in the lower right-hand corner of the label and be set in 12-point type or smaller.
(ii) The energy use disclosure labels required by the governments of Canada or Mexico may appear directly adjoining this label, as desired by the manufacturer.
(iii) The manufacturer may include the ENERGY STAR logo on the label for certified products in a location consistent with the sample labels in appendix L to this part. The logo must be no larger than 1 inch by 3 inches in size. Only manufacturers that have signed a Memorandum of Understanding with the Department of Energy or the Environmental Protection Agency may add the ENERGY STAR logo to labels on qualifying covered products; such manufacturers may add the ENERGY STAR logo to labels only on those covered products that are contemplated by the Memorandum of Understanding.

16 C.F.R. §305.20

72 FR 49969 , Aug. 29, 2007, as amended at 78 FR 2208 , Jan. 10, 2013; 78 FR 8374 , Feb. 6, 2013; 78 FR 43982 , July 23, 2013; 79 FR 77870 , Dec. 29, 2014; 81 FR 63648 , Sept. 15, 2016; 83 FR 7596 , Feb. 22, 2018. Redesignated at 84 FR 58029 , Oct. 30, 2019, as amended at 84 FR 58037 , Oct. 30, 2019; 86 FR 9283 , Feb. 12, 2021
82 FR 29236 , 12/26/2017; 84 FR 58037 , 11/29/2019; 86 FR 9283 , 1/1/2023