10 C.F.R. § 460.102

Current through September 30, 2024
Section 460.102 - Building thermal envelope requirements
(a)Compliance options. The building thermal envelope must meet either the prescriptive requirements of paragraph (b) of this section or the performance requirements of paragraph (c) of this section.
(b)Prescriptive requirements.
(1) The building thermal envelope must meet the applicable minimum R-value (nominal value of insulation), and the glazing maximum U-factor and SHGC, requirements set forth in table 1 to § 460.102(b)(1) and table 2 to § 460.102(b)(2) or component U-values set forth in table 3 to § 460.102(b)(5) and table 4 to § 460.102(b)(5) .

Table 1 to § 460.102(b)(1) -Tier 1 Building Thermal Envelope Prescriptive Requirements

Climate zoneExterior wall
insulation
R-value
Exterior ceiling
insulation
R-value
Exterior floor
insulation
R-value
Window
U-factor
Skylight
U-factor
Door
U-factor
Glazed
fenestration
SHGC
11322221.080.750.400.7
21322190.50.550.400.6
31922220.350.550.40Not applicable.

Table 2 to § 460.102(b)(1) -Tier 2 Building Thermal Envelope Prescriptive Requirements

Climate zoneExterior wall
insulation
R-value
Exterior ceiling
insulation
R-value
Exterior floor
insulation
R-value
Window
U-factor
Skylight
U-factor
Door
U-factor
Glazed
fenestration
SHGC
11330130.320.750.400.33
22130190.300.550.400.25
32138300.300.550.40Not applicable.

(2) For the purpose of compliance with the exterior ceiling insulation R-value requirement of paragraph (b)(1) of this section, the truss heel height must be a minimum of 5.5 inches at the outside face of each exterior wall.
(3) A combination of R-21 batt insulation and R-14 blanket insulation may be used for the purpose of compliance with the floor insulation R-value requirement of table 2 to § 460.102(b)(1) , Climate Zone 3.
(4) An individual skylight that has an SHGC that is less than or equal to 0.30 is not subject to the glazed fenestration SHGC requirements established in paragraph (b)(1) of this section. Adapted from section R402 of the 2021 IECC.
(5)U- factor alternatives to R-value requirements. Compliance with the applicable requirements in paragraph (b)(1) of this section may be determined using the applicable maximum U-factor values set forth in table 3 to § 460.102(b)(5) and table 4 to § 460.102(b)(5) , which reflect the thermal transmittance of the component, excluding fenestration, and not just the insulation of that component, as an alternative to the minimum nominal R-value requirements set forth in table 1 to § 460.102(b)(1) and table 2 to § 460.102(b)(1) , respectively.

Table 3 to § 460.102(b)(5) -U-Factor Alternatives to Tier 1 R-Value Requirements

Climate zone Exterior ceiling
U-factor
Exterior wall
U-factor
Exterior floor
U-factor
10.0610.0940.049
20.0610.0940.056
30.0610.0680.049

Table 4 to § 460.102(b)(5) -U-Factor Alternatives to Tier 2 R-Value Requirements

Climate zone Exterior ceiling
U-factor
Exterior wall
U-factor
Exterior floor
U-factor
10.0430.0940.078
20.0430.0630.056
30.0370.0630.032

(c)Performance requirements.
(1) The building thermal envelope must have a Uo that is less than or equal to the applicable value specified in table 5 to § 460.102(c)(1) and table 6 to § 460.102(c)(1) .

Table 5 to § 460.102(c)(1) -Tier 1 Building Thermal Envelope Performance Requirements

Climate zone Single-section
Uo
10.110
20.091
30.074

Table 6 to § 460.102(c)(1) -Tier 2 Building Thermal Envelope Performance Requirements

Climate zone Multi-section
Uo
10.082
20.066
30.055

(2) Area-weighted average vertical fenestration U-factor must not exceed 0.48 in Climate Zone 2 or 0.40 in Climate Zone 3. Adapted from section R402 of the 2021 IECC.
(3) Area-weighted average skylight U-factor must not exceed 0.75 in Climate Zone 2 and Climate Zone 3. Adapted from section R402 of the 2021 IECC.
(4) Windows, skylights and doors containing more than 50 percent glazing by area must satisfy the SHGC requirements established in paragraph (b)(1) of this section on the basis of an area-weighted average. Adapted from section R402 of the 2021 IECC.
(d) [Reserved].
(e)Determination of compliance with paragraph (c) of this section.
(1)Uo must be determined in accordance with Overall U-Values and Heating/Cooling Loads-Manufactured Homes (incorporated by reference; see § 460.3 )
(2) [Reserved]

10 C.F.R. §460.102

87 FR 32818, 8/1/2022