Single-phase | Three-phase | ||
kVA | % | kVA | % |
15 | 97.7 | 15 | 97.0 |
25 | 98.0 | 30 | 97.5 |
37.5 | 98.2 | 45 | 97.7 |
50 | 98.3 | 75 | 98.0 |
75 | 98.5 | 112.5 | 98.2 |
100 | 98.6 | 150 | 98.3 |
167 | 98.7 | 225 | 98.5 |
250 | 98.8 | 300 | 98.6 |
333 | 98.9 | 500 | 98.7 |
750 | 98.8 | ||
1000 | 98.9 |
Note 1 to paragraph (a)(1): All efficiency values are at 35 percent per-unit load.
Table 2 to Paragraph (a)(1)
Single-phase | Three-phase | ||
kVA | kVA | ||
15 | 97.70 | 15 | 97.89 |
25 | 98.00 | 30 | 98.23 |
37.5 | 98.20 | 45 | 98.40 |
50 | 98.30 | 75 | 98.60 |
75 | 98.50 | 112.5 | 98.74 |
100 | 98.60 | 150 | 98.83 |
167 | 98.70 | 225 | 98.94 |
250 | 98.80 | 300 | 99.02 |
333 | 98.90 | 500 | 99.14 |
750 | 99.23 | ||
1000 | 99.28 |
Note: All efficiency values are at 35 percent of nameplate-rated load, determined according to the DOE Test Method for Measuring the Energy Consumption of Distribution Transformers under appendix A to this subpart K.
Table 3 to Paragraph (a)(3)
Single-phase | Three-phase | ||
kVA | Efficiency (%) | kVA | Efficiency (%) |
15 | 98.39 | 15 | 98.31 |
25 | 98.60 | 30 | 98.58 |
37.5 | 98.74 | 45 | 98.72 |
50 | 98.81 | 75 | 98.88 |
75 | 98.95 | 112.5 | 98.99 |
100 | 99.02 | 150 | 99.06 |
167 | 99.09 | 225 | 99.15 |
250 | 99.16 | 300 | 99.22 |
333 | 99.23 | 500 | 99.31 |
750 | 99.38 | ||
1000 | 99.42 |
Note: All efficiency values are at 35 percent of nameplate-rated load, determined according to the DOE Test Method for Measuring the Energy Consumption of Distribution Transformers under appendix A to this subpart K.
Single-phase | Three-phase | ||
kVA | Efficiency (%) | kVA | Efficiency (%) |
10 | 98.62 | 15 | 98.36 |
15 | 98.76 | 30 | 98.62 |
25 | 98.91 | 45 | 98.76 |
37.5 | 99.01 | 75 | 98.91 |
50 | 99.08 | 112.5 | 99.01 |
75 | 99.17 | 150 | 99.08 |
100 | 99.23 | 225 | 99.17 |
167 | 99.25 | 300 | 99.23 |
250 | 99.32 | 500 | 99.25 |
333 | 99.36 | 750 | 99.32 |
500 | 99.42 | 1000 | 99.36 |
667 | 99.46 | 1500 | 99.42 |
833 | 99.49 | 2000 | 99.46 |
2500 | 99.49 |
Note 3 to paragraph (b)(1): All efficiency values are at 50 percent per-unit load.
Table 5 to Paragraph (b)(2)
Single-phase | Three-phase | ||
kVA | Efficiency (%) | kVA | Efficiency (%) |
10 | 98.70 | 15 | 98.65 |
15 | 98.82 | 30 | 98.83 |
25 | 98.95 | 45 | 98.92 |
37.5 | 99.05 | 75 | 99.03 |
50 | 99.11 | 112.5 | 99.11 |
75 | 99.19 | 150 | 99.16 |
100 | 99.25 | 225 | 99.23 |
167 | 99.33 | 300 | 99.27 |
250 | 99.39 | 500 | 99.35 |
333 | 99.43 | 750 | 99.40 |
500 | 99.49 | 1000 | 99.43 |
667 | 99.52 | 1500 | 99.48 |
833 | 99.55 | 2000 | 99.51 |
2500 | 99.53 |
Note: All efficiency values are at 50 percent of nameplate-rated load, determined according to the DOE Test-Procedure, appendix A to this subpart K.
Table 6 to Paragraph (b)(3)
Single-phase | Three-phase | ||
kVA | Efficiency (%) | kVA | Efficiency (%) |
10 | 98.77 | 15 | 98.92 |
15 | 98.88 | 30 | 99.06 |
25 | 99.00 | 45 | 99.14 |
37.5 | 99.10 | 75 | 99.22 |
50 | 99.15 | 112.5 | 99.29 |
75 | 99.23 | 150 | 99.33 |
100 | 99.29 | 225 | 99.38 |
167 | 99.46 | 300 | 99.42 |
250 | 99.51 | 500 | 99.38 |
333 | 99.54 | 750 | 99.43 |
500 | 99.59 | 1000 | 99.46 |
667 | 99.62 | 1500 | 99.51 |
833 | 99.64 | 2000 | 99.53 |
2500 | 99.55 | ||
3750 | 99.54 | ||
5000 | 99.53 | ||
Note: All efficiency values are at 50 percent of nameplate-rated load, determined according to the DOE Test Method for Measuring the Energy Consumption of Distribution Transformers under appendix A to this subpart K.
Table 7 to Paragraph (b)(4)
Single-phase | Three-phase | ||
kVA | Efficiency (%) | kVA | Efficiency (%) |
10 | 98.70 | 15 | 98.65 |
15 | 98.82 | 30 | 98.83 |
25 | 98.95 | 45 | 98.92 |
37.5 | 99.05 | 75 | 99.03 |
50 | 99.11 | 112.5 | 99.11 |
75 | 99.19 | 150 | 99.16 |
100 | 99.25 | 225 | 99.23 |
167 | 99.33 | 300 | 99.27 |
250 | 99.39 | 500 | 99.35 |
333 | 99.43 | 750 | 99.40 |
500 | 99.49 | 1000 | 99.43 |
667 | 99.52 | 1500 | 99.48 |
833 | 99.55 | 2000 | 99.51 |
2500 | 99.53 |
Note: All efficiency values are at 50 percent of nameplate-rated load, determined according to the DOE Test-Procedure, appendix A to this subpart K.
Single-phase | Three-phase | ||||||
kVA | BIL* | kVA | BIL | ||||
20-45 kV | 46-95 kV | [GREATER THAN EQUAL TO]96 kV | 20-45 kV | 46-95 kV | [GREATER THAN EQUAL TO]96 kV | ||
Efficiency (%) | Efficiency (%) | Efficiency (%) | Efficiency (%) | Efficiency (%) | Efficiency (%) | ||
15 | 98.10 | 97.86 | 15 | 97.50 | 97.18 | ||
25 | 98.33 | 98.12 | 30 | 97.90 | 97.63 | ||
37.5 | 98.49 | 98.30 | 45 | 98.10 | 97.86 | ||
50 | 98.60 | 98.42 | 75 | 98.33 | 98.12 | ||
75 | 98.73 | 98.57 | 98.53 | 112.5 | 98.49 | 98.30 | |
100 | 98.82 | 98.67 | 98.63 | 150 | 98.60 | 98.42 | |
167 | 98.96 | 98.83 | 98.80 | 225 | 98.73 | 98.57 | 98.53 |
250 | 99.07 | 98.95 | 98.91 | 300 | 98.82 | 98.67 | 98.63 |
333 | 99.14 | 99.03 | 98.99 | 500 | 98.96 | 98.83 | 98.80 |
500 | 99.22 | 99.12 | 99.09 | 750 | 99.07 | 98.95 | 98.91 |
667 | 99.27 | 99.18 | 99.15 | 1000 | 99.14 | 99.03 | 98.99 |
833 | 99.31 | 99.23 | 99.20 | 1500 | 99.22 | 99.12 | 99.09 |
2000 | 99.27 | 99.18 | 99.15 | ||||
2500 | 99.31 | 99.23 | 99.20 |
* BIL means basic impulse insulation level.
Note 5 to paragraph (c)(1): All efficiency values are at 50 percent per-unit load.
Table 9 to Paragraph (c)(2)
kVA | Single-phase | kVA | Three-phase | ||||
BIL 1 | BIL | ||||||
20-45 kV | 46-95 kV | [GREATER THAN EQUAL TO]96 kV | 20-45 kV | 46-95 kV | [GREATER THAN EQUAL TO]96 kV | ||
Efficiency (%) | Efficiency (%) | Efficiency (%) | Efficiency (%) | Efficiency (%) | Efficiency (%) | ||
15 | 98.10 | 97.86 | 15 | 97.50 | 97.18 | ||
25 | 98.33 | 98.12 | 30 | 97.90 | 97.63 | ||
37.5 | 98.49 | 98.30 | 45 | 98.10 | 97.86 | ||
50 | 98.60 | 98.42 | 75 | 98.33 | 98.13 | ||
75 | 98.73 | 98.57 | 98.53 | 112.5 | 98.52 | 98.36 | |
100 | 98.82 | 98.67 | 98.63 | 150 | 98.65 | 98.51 | |
167 | 98.96 | 98.83 | 98.80 | 225 | 98.82 | 98.69 | 98.57 |
250 | 99.07 | 98.95 | 98.91 | 300 | 98.93 | 98.81 | 98.69 |
333 | 99.14 | 99.03 | 98.99 | 500 | 99.09 | 98.99 | 98.89 |
500 | 99.22 | 99.12 | 99.09 | 750 | 99.21 | 99.12 | 99.02 |
667 | 99.27 | 99.18 | 99.15 | 1000 | 99.28 | 99.20 | 99.11 |
833 | 99.31 | 99.23 | 99.20 | 1500 | 99.37 | 99.30 | 99.21 |
2000 | 99.43 | 99.36 | 99.28 | ||||
2500 | 99.47 | 99.41 | 99.33 |
1 BIL means basic impulse insulation level.
Note: All efficiency values are at 50 percent of nameplate rated load, determined according to the DOE Test Method for Measuring the Energy Consumption of Distribution Transformers under appendix A to this subpart K.
Table 10 to Paragraph (c)(3)
kVA | Single-phase | kVA | Three-phase | ||||
BIL 1 | BIL | ||||||
20-45 kV | 46-95 kV | [GREATER THAN EQUAL TO]96 kV | 20-45 kV | 46-95 kV | [GREATER THAN EQUAL TO]96 kV | ||
Efficiency (%) | Efficiency (%) | Efficiency (%) | Efficiency (%) | Efficiency (%) | Efficiency (%) | ||
15 | 98.29 | 98.07 | 15 | 97.75 | 97.46 | ||
25 | 98.50 | 98.31 | 30 | 98.11 | 97.87 | ||
37.5 | 98.64 | 98.47 | 45 | 98.29 | 98.07 | ||
50 | 98.74 | 98.58 | 75 | 98.50 | 98.32 | ||
75 | 98.86 | 98.71 | 98.68 | 112.5 | 98.67 | 98.52 | |
100 | 98.94 | 98.80 | 98.77 | 150 | 98.79 | 98.66 | |
167 | 99.06 | 98.95 | 98.92 | 225 | 98.94 | 98.82 | 98.71 |
250 | 99.16 | 99.06 | 99.02 | 300 | 99.04 | 98.93 | 98.82 |
333 | 99.23 | 99.13 | 99.09 | 500 | 99.18 | 99.09 | 99.00 |
500 | 99.30 | 99.21 | 99.18 | 750 | 99.29 | 99.21 | 99.12 |
667 | 99.34 | 99.26 | 99.24 | 1000 | 99.35 | 99.28 | 99.20 |
833 | 99.38 | 99.31 | 99.28 | 1500 | 99.43 | 99.37 | 99.29 |
2000 | 99.49 | 99.42 | 99.35 | ||||
2500 | 99.52 | 99.47 | 99.40 | ||||
3750 | 99.50 | 99.44 | 99.40 | ||||
5000 | 99.48 | 99.43 | 99.39 |
1 BIL means basic impulse insulation level/
Note: All efficiency values are at 50 percent of nameplate rated load, determined according to the DOE Test Method for Measuring the Energy Consumption of Distribution Transformers under appendix A to this subpart K.
10 C.F.R. §431.196