Cal. Code Regs. tit. 8 § 5492

Current through Register 2024 Notice Reg. No. 45, November 8, 2024
Section 5492 - Specific Requirements
(a) The location of liquefied hydrogen storage, as determined by the maximum total quantity of liquefied hydrogen, shall be in the order of preference as indicated by Roman numerals in the following Table H-3:

Table H-3

Maximum Total Quantity of Liquefied Hydrogen Storage Permitted

Size of Hydrogen Storage (Capacity in Gallons)

Nature of Location39.63 (150 liters) to 5051 to 300301 to 600In excess of 600
OutdoorsIIII
In a separate buildingIIIIIINot permitted
In a special roomIIIIIINot permittedNot permitted
Inside buildings not in a special room and exposed to other occupanciesIVNot permittedNot permittedNot permitted

NOTE: This table does not apply to the storage in dewars of the type generally used in laboratories for experimental purposes.

(b) The minimum distance in feet from liquefied hydrogen systems of indicated storage capacity located outdoors, in a separate building, or in a special room to any specified exposure shall be in accordance with Table H-4.

Table H-4

Minimum Distance (feet) from Liquefied Hydrogen Systems to Exposures

Liquefied Hydrogen Storage
Type of Exposure39.63 (150 liters) 3,5003,501 to 15,00015,001 to 30,000
1.Fire-resistive Building and Fire Walls*555
2.Noncombustible Building*255075
3.Other Buildings*5075100
4.Wall Openings, Air Compressor Intakes, Inlets for Air-Conditioning or Ventilating Equipment757575
5.Flammable Liquids (Above-ground and Vent or Fill Openings if Below Ground) (See 5491(c) and (d))5075100
6.Between Stationary Liquefied Hydrogen Containers555
7.Flammable Gas Storage5075100
8.Liquid Oxygen Storage and other Oxidizers (See 5491(c) and (d))100100100
9.Combustible Solids5075100
10.Open Flames, Smoking and Welding505050
11.Concentrations of People**757575
12.Public Ways, Railroads, and Property Lines255075

* Refer to NFPA No. 220, "Standard Types of Building Construction," for definitions of construction types.

** In congested areas such as offices, lunchrooms, locker rooms, time clock areas, and places of public assembly.

NOTE: 1: The distances in Nos. 2, 3, 5, 7, 8, 9 and 12, in Table 2, may be reduced where protective structures, such as fire walls equal to height of top of the container, to safeguard the liquefied hydrogen storage system, are located between the liquefied hydrogen storage installation and the exposure. (See definition of Outdoor Location, Section 5415.)

NOTE: 2: Where protective structures are provided, ventilation and confinement of product shall be considered. The 5-foot distance in Nos. 1 and 6 facilitates maintenance and enhances ventilation.

Cal. Code Regs. Tit. 8, § 5492

1. Amendment of Table H-4 filed 3-2-76; effective thirtieth day thereafter (Register 76, No. 10).