Table H-1
Size of Hydrogen System | |||
Nature of Location | Less than 3,000 CF | 3,000 CF to 15,000 CF | In Excess of 15,000 CF |
Outdoors | I | I | I |
In a separate building | II | II | II |
In a special room | III | III | Not Permitted |
Inside buildings not in a special room and exposed to other occupancies | IV | Not Permitted | Not Permitted |
Table H-2
Size of Hydrogen System | ||||||
Type of Outdoor Exposure | Less than 3,000 CF | 3,000 CF to 15,000 CF | In Excess of 15,000 CF | |||
1. | Building or | Wood Frame Construction* | 10 | 25 | 50 | |
Structure | Heavy Timber, Noncombustible or Ordinary Construction* | 0 | 10 | 25* | ||
Fire Resistive Construction* | 0 | 0 | 0 | |||
2. | Wall Openings | Not above any part of a system | 10 | 10 | 10 | |
Above any part of a system | 25 | 25 | 25 | |||
3. | Flammable liquids | 0-1,000 gallons | 10 | 25 | 25 | |
above ground | In excess of 1,000 gallons | 25 | 50 | 50 | ||
4. | Flammable liquids | Tank | 10 | 10 | 10 | |
below ground-- | ||||||
0-1,000 gallons | Vent or fill opening of tank | 25 | 25 | 25 | ||
5. | Flammable liquids | Tank | 20 | 20 | 20 | |
below ground-- | ||||||
in excess of 1,000 gallons | Vent or fill opening of tank | 25 | 25 | 25 | ||
6. | Flammable gas storage | 0-15,000 CF capacity | 10 | 25 | 25 | |
age, either high | ||||||
pressure or low pressure | in excess of 15,000 CF capacity | 25 | 50 | 50 | ||
7. | Oxygen Storage | 12,000 CF or less | Refer to NFPA No. 51, Gas Systems for Welding and Cutting | |||
More than 12,000 CF | Refer to NFPA No. 50, Bulk Oxygen Systems at Consumer Sites | |||||
8. | Fast burning solids such as ordinary lumber, excelsior or paper | 50 | 50 | 50 | ||
9. | Slow burning solids such as heavy timber or coal | 25 | 25 | 25 | ||
10. | Open flames and other sources of ignition | 25 | 25 | 25 | ||
11. | Air compressor intakes or inlets to ventilating or air-conditioning equipment | 50 | 50 | 50 | ||
12. | Concentration of people*** | 25 | 50 | 50 | ||
13. | Public Sidewalks | 15 | 15 | 15 | ||
14. | Line of adjoining property which may be built upon | 5 | 5 | 5 |
* Refer to NFPA No. 220, Standard Types of Building Construction for definitions of various types of construction.
** But not less than one-half the height of adjacent side wall of the structure.
*** In congested areas such as offices, lunchrooms, locker rooms, time-clock areas and places of public assembly.
Cal. Code Regs. Tit. 8, § 5473