Where flammable liquids are used in dipping and coating operations, the employer shall also comply with the requirements of Articles 136 and 137 and Sections 5143 and 5154, as applicable.
The employer shall comply with this subsection (a)(1) if: | And: |
*The flashpoint of the liquid is 199.4 °F (93 °C) or above | *The liquid is heated as part of the operation; or |
*A heated object is placed in the liquid. |
The class is determined by two factors: hazard potential designated by a letter from A to D, inclusive, and the rate of gas, vapor, or mist evolution designated by a number from 1 to 4, inclusive.
Where:
C is the concentration in parts per million of airborne solvent vapor from each component.
L is the time-weighted eight-hour exposure limit concentration in parts per million for each component. (See Section 5155 for TWA exposure limit values.)
Lm is the combined TWA exposure limit concentration for the airborne mixture of solvent vapors.
TABLE V-7 DETERMINATION OF HAZARD POTENTIAL
Time-Weighted Average Exposure Limit1 | |||
Hazard | Gas and Vapor | Mist | Flashpoint2 |
Classification | (ppm) | (mg/M3) | (°F) |
A | 0-10 | 0-.1 | -- |
B | 11-100 | .11-1.0 | Under 100 |
C | 101-500 | 1.1-10 | 100-200 |
D | Over 500 | Over 10 | Over 200 |
Notes:
1 As specified by Section 5155.
2 Closed-cup flashpoint; extensive flashpoint data are listed in the National Fire Protection Association Bulletin, NFPA 325M-1969.
TABLE V-8 DETERMINATION OF RATE OF GAS OR VAPOR EVOLUTION1
Rate Index | Liquid Temperature (°F) | Degrees Below Boiling Point (°F) | Relative Evaporation 2 (Time for 100% Evaporation) | |
1 | Over 200 | 0-20 | Fast (0-3 hours) | |
2 | 150-200 | 21-50 | Medium (3-12 hours) | |
3 | 94-149 | 51-100 | Slow (12-50 hours) | |
4 | Under 94 | Over 100 | Nil (Over 50 hours) |
NOTES:
1 In certain classes of equipment, specifically vapor degreasers, an internal condenser or vapor level thermostat is used to prevent the vapor from leaving the tank during normal operation. In such cases, rate of vapor evolution from the tank into the workroom is not dependent upon the factors listed in the Table, but rather upon abnormalities of operating procedure, such as carryout of vapors from excessively fast action, dragout of liquid by entrainment in parts, contamination of solvent by water and other materials, or improper heat balance. When operating procedure is excellent, effective rate of evolution may be taken as 4.
2 Relative evaporation times may be found in the Handbook of Organic Industrial Solvents, American Mutual Insurance Alliance (1972). The evaporation times given as rates in the Tables are the ratios of the time (in hours) required to evaporate the solvent, to the evaporation time (one hour) required for the same volume of ethyl ether. Evaporation times for solvents not listed in the handbook may be found in the article by A. K. Doolittle in Industrial and Engineering Chemistry, Anal. Ed.,Vol. 27, p. 1169 (1935).
In all cases, the minimum control velocities shall conform to those listed in the following Table V-9.
TABLE V-9 MINIMUM CONTROL VELOCITIES IN FEET PER MINUTE
Enclosing Hood | Canopy Hood2 | ||||
Class | One Open Side | Two Open Sides | Lateral1Exhaust | Three Open Sides | Four Open S ides |
A-1 and A-2 | 100 | 150 | 150 | Do not use. | Do not use. |
A-3 (Note 2), B-1, B-2, and C-1 | 75 | 100 | 100 | 125 | 175 |
B-3, C-2, and D-1 | 65 | 90 | 75 | 100 | 150 |
A-4 (Note 2), C-3, and D-2 | 50 | 75 | 50 | 75 | 125 |
B-4, C-4, D-3, and D-4 | General Room Ventilation Required. |
NOTES:
1 See Table V-10 for computation of ventilation rate.
2 Do not use canopy hood for Hazard Potential A processes.
A hood which projects over an entire tank and completely encloses at least two sides of the tank shall be considered to be an enclosing hood. A hood which does not project over the entire tank, and in which the direction of air movement is substantially horizontal, shall be considered to be a hood which ventilates laterally. Hoods that project over the entire tank, and which do not conform to the definition of enclosing hoods, shall be considered to be canopy hoods.
TABLE V-10 REQUIRED VENTILATION RATES IN CFM
Required Minimum Control | Cubic Feet Per Minute Per Square Foot to Maintain | ||||||
Velocity Feet Per Minute | Required Minimum Velocities at Following | ||||||
(From Table V-9) | (The ratio of tank width to the tank length, W/L)1 2 | ||||||
0.0-0.09 | 0.1-0.24 | 0.25-0.49 | 0.5-0.99 | 1.0-2.0 | |||
Hood along side or two parallel sides of tank when one hood is against a wall or baffle (Note 2). Also for a manifold along tank centerline | |||||||
(Note 3) | |||||||
50.......................... | ..........................50 | 60 | 75 | 90 | 100 | ||
75.......................... | ..........................75 | 90 | 110 | 130 | 150 | ||
100.......................... | ..........................100 | 125 | 150 | 175 | 200 | ||
150.......................... | ..........................150 | 190 | 225 | 260 | 300 | ||
Hood along one side or two parallel sides of free standing tank not against wall or baffle. | |||||||
50.......................... | ..........................75 | 90 | 100 | 110 | 125 | ||
75.......................... | ..........................110 | 130 | 150 | 170 | 190 | ||
100.......................... | ..........................150 | 175 | 200 | 225 | 250 | ||
150.......................... | ..........................225 | 260 | 300 | 340 | 375 | ||
Notes: | 1 It is not practicable to ventilate across the long dimension of a tank whose ratio W/L exceeds 2.0. It is undesirable to do so when W/L exceeds 1.0. For circular tanks with lateral exhaust aloing up to 1/2 the circumference, use W/L = 1.0: for over 1/2 the circumference use W/L = 0.5. | ||||||
2 A baffle is defined as a vertical plate, the same length as the tank, which extends above the liquid level to a height at least equal to the width of the tank. If the exhaust hood is on the side of a tank against a building wall or close to it, it is adequately baffled. | |||||||
3 Use W/2 as tank width in computing when manifold is along centerline, or when hoods are used on two parallel sides of a tank. | |||||||
Note: | Tank width (W) means the effective width over which the hood must pull air to operate (for example, where the hood face is set back from the edge of the tank, this set must be added in measuring tank width). The surface area of tanks can frequently be reduced, and better control obtained (particularly on conveyorized systems) by using covers extending from the upper edges of the slots toward the center of the tank. |
Cal. Code Regs. Tit. 8, § 5154
2. Amendments filed 7-16-76; effective thirtieth day thereafter (Register 76, No. 29).
3. Editorial correction in Table V-7 (Register 77, No. 41).
4. Change without regulatory effect amending subsection (j)(2) filed 7-17-90 pursuant to section 100, title 1, California Code of Regulations (Register 90, No. 39).
5. Change without regulatory effect amending subsection (e)(2) filed 12-11-2000 pursuant to section 100, title 1, California Code of Regulations (Register 2000, No. 50).
6. Change without regulatory effect amending subsection (j)(1) and NOTE filed 6-2-2011 pursuant to section 100, title 1, California Code of Regulations (Register 2011, No. 22).
7. New subsection (a)(1) filed 5-5-2014; operative 5-6-2014 pursuant to Government Code section 11343.4(b)(3) (Register 2014, No. 19).
8. Editorial correction of subsection (a) (Register 2016, No. 46).
9. Editorial correction of subsection (a)(1) (Register 2018, No. 48).
10. Change without regulatory effect amending subsection (a)(1) filed 8-26-2019 pursuant to section 100, title 1, California Code of Regulations (Register 2019, No. 35).
Note: Authority cited: Section 142.3, Labor Code. Reference: Section 142.3, Labor Code.
2. Amendments filed 7-16-76; effective thirtieth day thereafter (Register 76, No. 29).
3. Editorial correction in Table V-7 (Register 77, No. 41).
4. Change without regulatory effect amending subsection (j)(2) filed 7-17-90 pursuant to section 100, title 1, California Code of Regulations (Register 90, No. 39).
5. Change without regulatory effect amending subsection (e)(2) filed 12-11-2000 pursuant to section 100, title 1, California Code of Regulations (Register 2000, No. 50).
6. Change without regulatory effect amending subsection (j)(1) and Note filed 6-2-2011 pursuant to section 100, title 1, California Code of Regulations (Register 2011, No. 22).
7. New subsection (a)(1) filed 5-5-2014; operative 5/6/2014 pursuant to Government Code section 11343.4(b)(3) (Register 2014, No. 19).
8. Editorial correction of subsection (a) (Register 2016, No. 46).
9. Editorial correction of subsection (a)(1) (Register 2018, No. 48).
10. Change without regulatory effect amending subsection (a)(1) filed 8-26-2019 pursuant to section 100, title 1, California Code of Regulations (Register 2019, No. 35).