Exposed energized parts above workspace and above areas where persons may normally walk or stand shall be maintained at elevations not less than that required by the following table:
Table 2934 - Elevation of Unguarded Live Parts above Workspace
NOMINAL VOLTAGE | ELEVATION | |
BETWEENPHASES | Feet | Meters |
601-7500 | 9.01 | 2.81 |
7501-35kV | 9.0 | 2.8 |
Over 35kv | 9 feet + 0.37 inch/kv | 2.8 + 9.5 mm/kV |
above 35kv | over 35 kV |
1 The minimum elevation may be 8.5 ft. (2.6 m) for installations built before April 1, 2009.