Cal. Code Regs. tit. 8 § 1605.6

Current through Register 2024 Notice Reg. No. 25, June 21, 2024
Section 1605.6 - Guying
(a) Towers shall be secured with guys or rigid braces at each corner at intervals not to exceed 30 feet vertically.
(b) Towers guys shall be at least ½ -inch diameter improved plow-steel wire rope, secured to anchorages with wire-rope clips as specified in Table 5, or the equivalent. The wire-rope fastenings and the anchorages shall withstand four times the maximum intended loadings.

Cal. Code Regs. Tit. 8, § 1605.6