(f) Within this subsection, tanks shall be classified as follows: Class A--Tanks with fixed steel roofs but excluding steel water-seal roofs.
Class B--Tanks with nonmetal roofs.
Class C--Tanks with steel water-seal roofs.
Walkways and platforms on tank roofs required by subsections (b) and (c) of this Section, and the railings and toeboards, shall be provided as follows:
(1) The roofs of tanks in Class A shall have walkways as follows: (A) Tank roofs having a thickness less than one-eighth inch (1/8") shall not be used as a walkway regardless of the slope of the roof. In measuring the thickness of metal roofs, allowance shall be made for manufacturers tolerances.(B) Tank roofs having a slope of two inches (2") per foot or less may be used as a walkway. Such walkways shall be clearly defined by color contrast and if the slope of the tank roof is one inch (1") per foot or greater, the walkway shall have a nonskid surface.(C) Tank roofs having a slope greater than two inches (2") per foot shall be provided with independent walkways of steel or wood construction.(2) The roofs of tanks in Class B and C shall have independent walkways of metal or wood construction.(3) No independent walkways on a tank roof of Class A or B shall have a slope greater than three inches (3") per foot.(4) No walkway on a tank roof of Class A or B shall have a transverse slope greater than two inches (2") per foot.(5) Walkways on tank roofs shall be not less than twenty-four inches (24") in width but it shall be permissible to install midrails and toeboards within this width provided, however, that a minimum clear width of twenty inches (20") shall be maintained. Walkways shall be designed to carry the load to the supporting structure of the tank roof and shall be securely attached to the tank. Walkways constructed of steel shall have a nominal thickness not less than one-eighth inch (1/8"). Walkways shall be of sufficient strength to safely support the loads imposed on them.(6) Platforms on tanks of Class A, B and C shall be at least the equivalent in safety of the type of walkway required for the tank class.(7) Tanks in Class A, B, and C, the roofs of which are five feet (5') or more above ground or floor level, shall have those portions of their walkway and platform edges that are within six feet (6') of the roof edge equipped with railings and toeboards, or, as an alternative, railings and toeboards shall be installed on the tank edges which are within six feet (6') of the walkways or platforms. Provided, however, that toeboards shall not be required on that side of a platform that faces the peak of the roof. Note: Authority cited: Section 142.3, Labor Code. Reference: Section 142.3, Labor Code.