Section 484 - Vaporizer Installation
(a) Surge tanks, gas-air mix tanks, etc., containing vapor only, shall be located at least 3 feet from important buildings and property lines. Such tanks operating at pressures exceeding 20 psi shall be located not less than 10 feet from any building opening, whereas such tanks exceeding 501 gallons shall be located not less than 25 feet from any building opening.
(b) The use of direct-fired container heaters is prohibited.