Cal. Code Regs. tit. 25 § 4520.2

Current through Register 2025 Notice Reg. No. 2, January 10, 2025
Section 4520.2 - Testing After Appliances Are Connected

After appliances are connected, the piping system shall be pressurized to not less than ten (10) inches nor more than fourteen (14) inches water column and the appliance connections tested for leakage with soapy water or bubble solution.

Cal. Code Regs. Tit. 25, § 4520.2

1. New section filed 9-19-2011; operative 10-19-2011 (Register 2011, No. 38).

Note: Authority cited: Section 18015, Health and Safety Code. Reference: Section 18025, Health and Safety Code.

1. New section filed 9-19-2011; operative 10-19-2011 (Register 2011, No. 38).