Section 4516.9 - LPG - System Design and Service-Line Pressure
(a) Systems shall be of the vapor-withdrawal type.
(b) Vapor, at a pressure not over eighteen (18) inches water column, shall be delivered from the container into the gas-supply connection.
(c) Container openings for vapor withdrawal shall be located in the vapor space when the container is in service or shall be provided with a suitable internal withdrawal tube which communicates with the vapor space in or near the highest point in the container when it is mounted in service position, with the commercial modular on a level surface. Containers shall be permanently and legibly marked in a conspicuous manner on the outside to show the correct mounting position and the position of the service outlet connection. The method of mounting in place shall be such as to minimize the possibility of an incorrect positioning of the container.