Horizontal.................... | ...................15 lb/ft2 |
Vertical (horizontal projection)........................... | ....................9 lb/ft2 uplift |
Unit stresses may be increased in accordance with the applicable accepted engineering practice standards.
Floor......................... | ...................L/240 |
Roof and Ceiling Members.................. | ...................L/180 |
Sidewalls....................... | ...................L/180 |
Where L = the clear span between supports or two times the length of a cantilever.
Wall.................................. | ..................................8.0 |
Ceiling................................... | ..................................16.0 |
Floor................................... | ..................................10.0 |
Wall................................... | ..................................20% of net wall area (less windows) |
Ceiling................................... | ..................................5% of total ceiling area |
Floor................................... | ..................................10% of net floor area (less duct area) |
Outside Design Temperature Degrees F | Infiltration Allowance Btu/hr | ||
40.......................... | ..........................3,330 | ||
30.......................... | ..........................4,440 | ||
20.......................... | ..........................5,550 | ||
10.......................... | ..........................6,660 | ||
0.......................... | ..........................7,770 | ||
minus | 10.......................... | ..........................8,880 | |
minus | 20.......................... | ..........................9,990 | |
minus | 30.......................... | ..........................11,100 | |
minus | 40.......................... | ..........................12,210 |
One person.............................. | ..............................50 |
Two persons............................... | ..............................70 |
Each person in excess of two............................... | ..............................50 |
Specific Hazardous Locations | Size of Individual Glazed Area | Requirements 2 |
Glazing in exit and entrance doors.......................... | Over 6 sq. ft. | Each glazed area shall pass |
the requirements of ANSI Standard Z97.1 3 if not protected by a protective grille 1 firmly attached to stiles on each exposed side. | ||
Glazing in storm doors.......................... | Over 2 sq. ft. | Each glazed area shall pass |
the requirements of ANSI Standard Z97.1 3 if not protected by a protective grille 1 firmly attached to stiles on each exposed side. | ||
Glazing in sliding exterior doors.......................... | All Sizes | Each glazed area shall pass |
the requirements of ANSI Standard Z97.1.3 | ||
Glazing in all unframed doors (swinging).......................... | All Sizes | Each glazed area shall be |
fully tempered glass and pass the requirements of ANSI Standard Z97.1.3 | ||
Glazing in shower doors and tub enclosures.......................... | All Sizes | Each glazed area shall pass |
the test requirements of ANSI Standard Z97.1.3 | ||
Other fixed glazed panels located within 12 inches on either side of exit and entrance doors.......................... | All Sizes | Each glazed area within 18 |
inches of the floor shall pass the requirements of ANSI Standard Z97.1 3 unless the glazed area is protected by a barrier within 12 inches immediately in front of the glazing. |
1 Shall be constructed and attached in such a manner so as to prevent human impact from being delivered to glass surface.
2 Annealed glass less than single strength (SS) in thickness shall not be used. If short dimension is larger than 24 inches, annealed glass must be double strength (DS) or thicker.
3 American National Standard Performance Specifications and Methods of Test for Safety Glazing Material Used in Buildings, as approved January 20, 1972, American National Standards Institute, 1430 Broadway, New York, New York 10018.
For the purpose of this article, a "smoke detector" is a device which detects visible or invisible particles of combustion. A "single station alarm device" is an assembly incorporating a detector and an alarm sounding device in one unit, operated from a power supply either in the unit or obtained at the point of installation. Detectors shall operate from an AC, monitored battery, or combination AC/battery power source.
Cal. Code Regs. Tit. 25, § 4049.3
2. Change without regulatory effect repealing subsections (c)-(c)(9) and amending NOTE filed 10-8-2008 pursuant to section 100, title 1, California Code of Regulations (Register 2008, No. 41).
Note: Authority cited: Section 18015, Health and Safety Code. Reference: Sections 18025, 18028, 18029.5 and 18031.5 Health and Safety Code.
2. Change without regulatory effect repealing subsections (c)-(c)(9) and amending Note filed 10-8-2008 pursuant to section 100, title 1, California Code of Regulations (Register 2008, No. 41).