Cal. Code Regs. tit. 25 § 2436

Current through Register 2024 Notice Reg. No. 50, December 13, 2024
Section 2436 - Electrical Installations
(a) Electrical equipment and installations within an accessory building or structure or building component and the circuit supplying power shall be installed by a permanent wiring method and shall comply with the requirements for electrical installations of this chapter.
(b) Flexible cord shall not be used to supply an accessory building or structure or building component, or as a substitute for the fixed wiring of an accessory building or structure or building component.
(c) Unless otherwise specified by this article, electrical service provided to an accessory building or structure or building component shall be supplied from the lot service equipment, provided:
(1) a permit is obtained to alter the lot electrical service by installing a separate overcurrent protective device rated not more than the total calculated electrical load, and
(2) the lot service equipment is capable of supplying the additional load, and
(3) the overcurrent protective device and its installation complies with the California Electrical Code.

Cal. Code Regs. Tit. 25, § 2436

1. New section filed 7-6-2004; operative 7-6-2004 pursuant to Government Code section 11343.4 (Register 2004, No. 28).

Note: Authority cited: Section 18865, Health and Safety Code. Reference: Sections 18871.3 and 18873.3, Health and Safety Code.

1. New section filed 7-6-2004; operative 7-6-2004 pursuant to Government Code section 11343.4 (Register 2004, No. 28).