(a) Each lot drain inlet shall be assigned a waste loading value of six (6) fixture units and each park drainage system shall be sized according to Table 2268-1 or as provided herein. Drainage laterals shall be not less than three (3) inches in diameter.(b) A park drainage system in which the grade, slope, or sizing of drainage pipe does not meet the minimums specified in Tables 2268-1 or 2268-2 shall be designed by a registered engineer for a minimum velocity flow of two (2) feet per second.(c) Park drainage systems installed without P-traps or vents may be sized for individually vented systems in accordance with Table 2268-1 for individually vented systems.(d) A park drainage system which exceeds the fixture unit loading of Table 2268-1 shall be designed by a registered engineer. Table 2268-1 |
Drainage Pipe Diameter and Number of Fixture Units on Drainage System |
|
| Maximum No. | Maximum No. | Terminal & |
| of Fixture Units | of Fixture Units | Relief Vent |
Size of Drainage | Individually | Wet Vented | Wet Vented |
Pipe (Inches) | Vented System | System | System (Inches) |
3 | 35 | 14 | 2 |
4 | 180 | 35 | 3 |
5 | 356 | 180 | 4 |
6 | 600 | 356 | 4 |
Table 2268-2 |
Minimum Grade and Slope of Drainage Pipe |
|
| Slope | | Slope |
Pipe Size | per 100 ft. | Pipe Size | per 100 ft. |
(inches) | (inches) | (inches) | (inches) |
| 2 | 25 | 6 | | 8 |
| 3 | 20 | 8 | | 4 |
| 4 | 15 | 10 | | 3 1/2 |
| 5 | 11 | 12 | | 3 |
Cal. Code Regs. Tit. 25, § 2268