Cal. Code Regs. tit. 25 § 2152

Current through Register 2024 Notice Reg. No. 50, December 13, 2024
Section 2152 - Ground-Fault Protection

Ground-fault protection of park service equipment shall be provided for solidly grounded wye electrical services of more than 150 volts to ground, but not exceeding 600 volts phase-to-phase for each service disconnecting means rated at 1,000 amperes or more. Each service disconnecting means rated 1000-amperes or more shall be performance tested when first installed, as required by the California Electrical Code, Section 230-95. The test shall be conducted in accordance with approved instructions, which shall be provided with the equipment. A written record of this test shall be made and shall be available to the enforcement agency.

Cal. Code Regs. Tit. 25, § 2152

1. New section filed 7-6-2004; operative 7-6-2004 pursuant to Government Code section 11343.4 (Register 2004, No. 28).
2. Amendment filed 7-22-2005; operative 7-22-2005 pursuant to Government Code section 11343.4 (Register 2005, No. 29).
3. Editorial correction of HISTORY 2 (Register 2005, No. 33).

Note: Authority cited: Section 18865, Health and Safety Code. Reference: Section 18873.3, Health and Safety Code.

1. New section filed 7-6-2004; operative 7-6-2004 pursuant to Government Code section 11343.4 (Register 2004, No. 28).
2. Amendmentfiled 7-22-2005; operative 7-22-2005 pursuant to Government Code section 11343.4 (Register 2005, No. 29).
3. Editorial correction of History 2 (Register 2005, No. 33).