Current through Register 2024 Notice Reg. No. 45, November 8, 2024
Section 1220 - Lot Gas Shutoff Valve(a) Each lot shall have a gas shutoff valve, listed for its intended use by a department-approved listing agency, installed in a readily accessible location upstream of the lot gas outlet.(b) The valve shall be located on the lot gas riser outlet at a height of not less than six (6) inches above grade.(c) The lot gas shutoff valve shall not be located under or within any unit, or accessory building or structure. EXCEPTION: gas shut-off valves may be located under an awning or carport that is not enclosed complying with Article 9 of this chapter.
(d) Whenever the lot gas riser outlet is not in use, it shall be closed with an approved cap or plug to prevent accidental discharge of gas.Cal. Code Regs. Tit. 25, § 1220
1. Amendment of section heading and section filed 7-6-2004; operative 7-6-2004 pursuant to Government Code section 11343.4 (Register 2004, No. 28). Note: Authority cited: Section 18300, Health and Safety Code. Reference: Section 18690, Health and Safety Code.
1. Amendment of section heading and section filed 7-6-2004; operative 7-6-2004 pursuant to Government Code section 11343.4 (Register 2004, No. 28).