Section 1152 - Ground-Fault Protection

Ground-fault protection of park service equipment shall be provided for solidly grounded wye electrical services of more than 150 volts to ground, but not exceeding 600 volts phase-to-phase for each service disconnecting means rated at 1,000 amperes or more. Each service disconnecting means rated 1000-amperes or more shall be performance tested when first installed, as required by the California Electrical Code, section 230-95. The test shall be conducted in accordance with approved instructions, which shall be provided with the equipment. A written record of this test shall be made and shall be available to the enforcement agency.