Section 60315 - Design Requirements

The public water supply shall not be used as a backup or supplemental source of water for a dual-plumbed recycled water system unless the connection between the two systems is protected by an air gap separation which complies with the requirements of sections 7602(a) and 7603(a) of title 17, California Code of Regulations, and the approval of the public water system has been obtained.