Cal. Code Regs. tit. 22 § 60301.220

Current through Register 2024 Notice Reg. No. 24, June 14, 2024
Section 60301.220 - Disinfected Secondary-2.2 Recycled Water

"Disinfected secondary-2.2 recycled water" means recycled water that has been oxidized and disinfected so that the median concentration of total coliform bacteria in the disinfected effluent does not exceed a most probable number (MPN) of 2.2 per 100 milliliters utilizing the bacteriological results of the last seven days for which analyses have been completed, and the number of total coliform bacteria does not exceed an MPN of 23 per 100 milliliters in more than one sample in any 30 day period.

Cal. Code Regs. Tit. 22, § 60301.220

1. New section filed 11-2-2000; operative 12-2-2000 (Register 2000, No. 44).

Note: Authority cited: Section 13521, Water Code. Reference: Sections 13520 and 13521, Water Code.