Table 64664-A
Combined Filter Effluent Data for Monthly Report
If a supplier uses... | The supplier shall report... |
(1) Conventional or direct filtration treatment and serves 10,000 or more persons(a) | The total number of turbidity measurements and either: |
(A) The turbidity achieved 50, 90, 95, 98, and 99 percent of the time that the plant was producing water; and the date, time, and value of any turbidity measurements that exceed 1.0 NTU; or | |
(B) The results of turbidity measurements recorded at intervals no greater than every four hours; all results that exceed 0.3 NTU, recorded at intervals no greater than every 15 minutes; and the number and percent of turbidity measurements that are less than or equal to 0.3 NTU, based on measurements recorded at intervals no greater than every 15 minutes. | |
(2) Conventional or direct filtration treatment and serves fewer than 10,000 persons(b), diatomaceous earth filtration, slow sand filtration(c), or an alternative filtration technology | (A) The total number of turbidity measurements; |
(B) The results of turbidity measurements; | |
(C) The number and percent of turbidity measurements taken that are less than or equal to the performance standard specified for each filtration technology in section 64653 or as required for an alternative treatment process; | |
(D) The date, time, and value of any turbidity measurements that exceed performance levels specified in section 64653 or as required for an alternative treatment process; and | |
(E) The average daily turbidity level. | |
__________________________________________________ | |
(a) A supplier shall review the data reported to ensure that it is not compromised by system or instrument maintenance, hardware or software problems, signal transmission problems, or for other technical reasons. | |
(b) A supplier monitoring pursuant to footnote (c) of table 64655 may report pursuant to paragraph (1)(A) in lieu of paragraphs (2)(B) through (2)(E). | |
(c) If the turbidity of the combined filter effluent is greater than 1.0 NTU in five percent or more of the measurements, a supplier shall also report the dates and results of total coliform sampling of the combined filter effluent prior to disinfection to demonstrate compliance with paragraph (4)(A) of table 64653. |
Table 64664-B
Individual Filter Data for Monthly Report
If a supplier uses... | The supplier shall report... |
(1) Conventional or direct filtration treatment and serves 10,000 or more persons | (A) Certification that individual filter turbidity monitoring was conducted pursuant to section 64655; |
(B) For an exceedance of section 64660(b)(7)(A), (b)(7)(B), or (b)(7)(C), a written explanation of the cause of the exceedance; | |
(C) For an exceedance of section 64660(b)(7)(D) or (b)(7)(E), the filter number, turbidity measurements, and date(s) and time(s) of the exceedance(s); and either: | |
1. The obvious reason for the exceedance; or | |
2. If the supplier is not able to identify an obvious reason for the abnormal filter performance, the filter profile produced pursuant to table 64660; and | |
(D) For an exceedance of section 64660(b)(7)(F), certification that a self-assessment was conducted pursuant to table 64660. | |
(2) Conventional or direct filtration treatment and serves fewer than 10,000 persons | (A) The information in paragraphs (1)(A) and (1)(B); |
(B) For an exceedance of section 64660(b)(7)(D) or (b)(7)(E), the filter number, turbidity measurements, date(s) and time(s) of the exceedance(s); and, if known, the obvious reason for the exceedance. | |
(C) For an exceedance of section 64660(b)(7)(F), the date the self-assessment was triggered and completed. If the self-assessment was triggered during the last four days of the month, the supplier may report to the State Board by the 14th of the following month the date the self-assessment was triggered and completed; and | |
(D) For an exceedance of section 64660(b)(7)(G), certification that the CPE is required and the date it was triggered. |
Where V = the percent of distribution system samples with a detectable residual,
A = the value in paragraph (2)(A) of this subsection,
B = the value in paragraph (2)(B) of this subsection,
C = the value in paragraph (2)(C) of this subsection,
D = the value in paragraph (2)(D) of this subsection, and
E = the value in paragraph (2)(E) of this subsection, and
Cal. Code Regs. Tit. 22, § 64664
2. Amendment of subsection (c)(2)(F), new subsections (d)-(d)(4), subsection relettering, amendment of newly designated subsection (e), new subsection (g) and amendment of NOTE filed 12-13-2007; operative 1-12-2008 (Register 2007, No. 50).
3. Amendment of section and NOTE filed 5-22-2013; operative 7-1-2013 (Register 2013, No. 21).
4. Change without regulatory effect amending subsections (a), (b)(2)(C) and (c)(1) and amending NOTE filed 6-2-2015 pursuant to section 100, title 1, California Code of Regulations (Register 2015, No. 23).
Note: Authority cited: Sections 116271, 116350 and 116375, Health and Safety Code. Reference: Sections 116350 and 116375, Health and Safety Code.
2. Amendment of subsection (c)(2)(F), new subsections (d)-(d)(4), subsection relettering, amendment of newly designated subsection (e), new subsection (g) and amendment of Note filed 12-13-2007; operative 1-12-2008 (Register 2007, No. 50).
3. Amendment of section and Note filed 5-22-2013; operative 7-1-2013 (Register 2013, No. 21).
4. Change without regulatory effect amending subsections (a), (b)(2)(C) and (c)(1) and amending Note filed 6-2-2015 pursuant to section 100, title 1, California Code of Regulations (Register 2015, No. 23).