Cal. Code Regs. tit. 22 § 64576

Current through Register 2024 Notice Reg. No. 45, November 8, 2024
Section 64576 - Air-Release, Air Vacuum, and Combination Valves

Each new air-release, air vacuum, or combination valve, and any such valve installed to replace an existing valve shall be:

(a) Installed such that its vent opening is above grade, above the calculated 100-year flood water level, and, if recorded data are available, above the highest recorded water level;
(b) Readily accessible for inspection, maintenance and replacement;
(c) Constructed and designed to prevent exposure to rainwater or runoff, vandalism, and birds, insects, rodents, or other animals;
(d) Fitted with a downward-facing screened vent or a domed and screened cap; and
(e) Installed pursuant to American Water Works Association Standard C512-04 and Manual M51 (2001), which are hereby incorporated by reference.

Cal. Code Regs. Tit. 22, § 64576

1. New section filed 2-8-2008; operative 3-9-2008 (Register 2008, No. 6).

Note: Authority cited: Sections 116350, 116375 and 131200, Health and Safety Code. Reference: Sections 116275, 116375, 116535 and 131051, Health and Safety Code.

1. New section filed 2-8-2008; operative 3-9-2008 (Register 2008, No. 6).