Cal. Code Regs. tit. 19 § 1237.2

Current through Register 2024 Notice Reg. No. 19, May 10, 2024
Section 1237.2 - Fire Resistance

(Large Scale Test). The treated fabric, both before and after water extraction, shall be tested in accordance with the method outlined in Section 1237.3 below, and shall not continue to flame for more than two (2) seconds after the burner is removed. The vertical spread of flame and afterglow (smoldering combustion), as indicated by the length of char above the tip of the test flame, shall not exceed ten inches (10").

Cal. Code Regs. Tit. 19, § 1237.2

1. New section filed 11-10-60; effective thirtieth day thereafter (Register 60, No. 23).
1. New section filed 11-10-60; effective thirtieth day thereafter (Register 60, No. 23).