EXCEPTION: Extinguishers of lesser rating, desired for small specific hazards within the general hazard area, may be used, but shall not be considered as fulfilling any part of the requirements of Table 3.
Table 3
Type of Hazard | Basic Minimum Extinguisher Rating | Maximum Travel Distance to Extinguishers (in feet) | (in meters) |
Light (low) | 5B | 30 | 9.15 |
10B | 50 | 15.25 | |
Ordinary (moderate) | 10B | 30 | 9.15 |
20B | 50 | 15.25 | |
Extra (high) | 40B | 30 | 9.15 |
80B | 50 | 15.25 |
NOTE 1: The specified rating does not imply that fires of the magnitudes indicated by these ratings will occur, but rather to give the operators more time and agent to handle difficult spill fires that may occur.
NOTE 2: For fires involving water soluble flammable liquids see Section 566(d).
NOTE 3: For specific hazard applications see Section 566.
Cal. Code Regs. Tit. 19, § 569
2. Repealer and new section filed 3-4-92; operative 4-3-92 (Register 92, No. 15).
3. Repealer of subsection (d) filed 12-27-2001; operative 1-1-2002 pursuant to Government Code section 11343.4 (Register 2001, No. 52).
Note: Authority: Section 13160, Health and Safety Code. Reference: Section 13160, Health and Safety Code.
2. Repealer and new section filed 3-4-92; operative 4-3-92 (Register 92, No. 15).
3. Repealer of subsection (d) filed 12-27-2001; operative 1-1-2002 pursuant to Government Code section 11343.4 (Register 2001, No. 52).