Current through Register Vol. 30, No. 45, November 8, 2024
Section R9-33-202 - Fire Safety RequirementsA. The Department shall issue to an applicant or licensee:1. A fire risk prevention level 1 group home or behavioral-supported group home license if the group home or behavioral-supported group home meets the requirements in subsections (B) through (G); and2. A fire risk prevention level 2 group home or behavioral-supported group home license if the group home or behavioral-supported group home meets the requirements in subsections (B) through (H).B. A licensee shall ensure that the premises are in compliance with all applicable state and local fire safety regulations and that: 1. Before a license is issued or renewed, a fire inspection is conducted by the local fire department, the Department, or an entity authorized by the Department;2. Any repair or correction stated in a fire inspection report is made or corrected according to the requirements and time in the fire inspection report; and3. A current fire inspection report is available for review at the group home or behavioral-supported group home.C. A licensee shall ensure that the facility has at least one working, portable, all-purpose fire extinguisher labeled as rated at least 2A-10-BC by Underwriters Laboratories, or two co-located working, portable, all-purpose fire extinguishers labeled as rated at least 1A-10-BC by Underwriters Laboratories, installed and maintained in the facility as prescribed by the manufacturer or the fire authority having jurisdiction.D. A licensee shall ensure that a fire extinguisher:1. Is either: a. Disposable and has a charge indicator showing green or "ready" status; orb. Serviced at least once every 12 months by a fire extinguisher technician certified by the National Fire Protection Agency, the International Code Council, or Compliance Services and Assessments; and2. If serviced, is tagged specifying:a. The date of purchase or the date of recharging, whichever is more recent; andb. The name of the organization performing the service, if applicable.E. A licensee shall ensure that smoke detectors are:1. Working and audible at a level of 75db from the location of each bed used by a resident in the facility;2. Capable of alerting all residents in the facility, including a resident with a mobility or sensory impairment;3. Installed according to the manufacturer's instructions;4. Located in at least the following areas: b. Each room or hallway adjacent to a bedroom, except a bathroom or a laundry room; andc. Each room or hallway adjacent to the kitchen, except a bathroom, a pantry, or a laundry room; and5. If the licensee has been cited more than once in the previous four years under subsections (E)(1) through (4), either:a. Hard-wired to the electrical system of the group home or behavioral-supported group home with a battery backup; orb. Connected to an early-warning fire detection system required in subsection (H)(2), if applicable.F. A licensee shall ensure that each bedroom has at least one functional openable window or door to the outside for use as an emergency exit.G. A licensee shall ensure that: 1. A usable fireplace is covered by a protective screen or covering at all times; and2. Combustible or flammable materials are not stored within three feet of a furnace, heater, water heater, or usable fireplace.H. A licensee of a fire risk prevention level 2 group home or behavioral-supported group home shall ensure that:1. The facility contains an emergency lighting system that:a. Works without in-house electrical power,b. Illuminates the path of evacuation, andc. Is inspected at least once every 12 months by the manufacturer or an entity that installs and repairs emergency lighting systems;2. The facility has an early-warning fire detection system that:b. Is hard-wired or connected wirelessly, with battery back-up;c. Sounds every alarm in the facility when smoke is detected;d. Is installed in each bedroom, each room or each hallway adjacent to a bedroom, and each room or each hallway adjacent to a kitchen; ande. Is inspected at least once every 12 months by the manufacturer or by an entity that installs and repairs early-warning fire detection systems;3. The facility has one of the following: a. Sufficient staff on duty to evacuate all residents present at the facility within three minutes or, if applicable under R9-33-201(D), within five minutes; orb. An automatic sprinkler system installed according to the applicable standard incorporated by reference in A.A.C. R9-1-412 and installed according to NFPA 13, NFPA 13R, or NFPA 13D, as applicable, that:i. Covers every room in the facility; andii. Is inspected at least once every 12 months by the manufacturer or by an entity that installs and repairs automatic sprinkler systems; and4. Documentation is available at the facility for two years after the date of an inspection: a. For:i. The emergency lighting system inspection required in subsection (H)(1)(c);ii. The early-warning fire detection system inspection required in subsection (H)(2)(e); andiii. If applicable, the automatic sprinkler system required in subsection (H)(3)(b)(ii); andb. That includes: i. The date of the inspection,ii. The name of the entity performing the inspection,iii. A tag on the system or a written report of the results of the inspection, andiv. A description of any repairs made to the system as a result of the inspection.Ariz. Admin. Code § R9-33-202
New Section made by final rulemaking at 8 A.A.R. 910, effective February 11, 2002 (Supp. 02-1). Amended by final rulemaking at 18 A.A.R. 3295, effective February 3, 2013 (Supp. 12-4). Amended by exempt rulemaking at 30 A.A.R. 2045, effective 7/1/2024.