Ariz. Admin. Code § 9-10-426

Current through Register Vol. 30, No. 24, June 14, 2024
Section R9-10-426 - Physical Plant Standards
A. An administrator shall ensure that:
1. A nursing care institution complies with:
a. The applicable physical plant health and safety codes and standards, incorporated by reference in R9-10-104.01, that were in effect on the date the nursing care institution submitted architectural plans and specifications to the Department for approval according to R9-10-104; and
b. The requirements for Existing Health Care Occupancies in National Fire Protection Association 101, Life Safety Code, incorporated by reference in R9-10-104.01;
2. The premises and equipment are sufficient to accommodate:
a. The services stated in the nursing care institution's scope of services, and
b. An individual accepted as a resident by the nursing care institution;
3. A nursing care institution is ventilated by windows or mechanical ventilation, or a combination of both;
4. The corridors are equipped with handrails on each side that are firmly attached to the walls and are not in need of repair;
5. No more than two individuals reside in a resident room unless:
a. The nursing care institution was operating before October 31, 1982; and
b. The resident room has not undergone a modification as defined in A.R.S. § 36-401;
6. A resident has a separate bed, a nurse call system, and furniture to meet the resident's needs in a resident room or suite of rooms;
7. A resident room has:
a. A window to the outside with window coverings for controlling light and visual privacy, and the location of the window permits a resident to see outside from a sitting position;
b. A closet with clothing racks and shelves accessible to the resident; and
c. If the resident room contains more than one bed, a curtain or similar type of separation between the beds for privacy; and
8. A resident room or a suite of rooms:
a. Is accessible without passing through another resident's room; and
b. Does not open into any area where food is prepared, served, or stored.
B. If a swimming pool is located on the premises, an administrator shall ensure that:
1. The swimming pool is enclosed by a wall or fence that:
a. Is at least five feet in height as measured on the exterior of the wall or fence;
b. Has no vertical openings greater that four inches across;
c. Has no horizontal openings, except as described in subsection (B)(1)(e);
d. Is not chain-link;
e. Does not have a space between the ground and the bottom fence rail that exceeds four inches in height; and
f. Has a self-closing, self-latching gate that:
i. Opens away from the swimming pool,
ii. Has a latch located at least 54 inches from the ground, and
iii. Is locked when the swimming pool is not in use; and
2. A life preserver or shepherd's crook is available and accessible in the pool area.
C. An administrator shall ensure that a spa that is not enclosed by a wall or fence as described in subsection (B)(1) is covered and locked when not in use.

Ariz. Admin. Code § R9-10-426

Adopted effective January 28, 1980 (Supp. 80-1). Section repealed by final rulemaking at 8 A.A.R. 2785, effective October 1, 2002 (Supp. 02-2). New Section R9-10-426made by exempt rulemaking at 19 A.A.R. 2015, effective October 1, 2013 (Supp. 13-2). Amended by exempt rulemaking at 20 A.A.R. 1409, effective 7/1/2014. Amended by final expedited rulemaking at 25 A.A.R. 3481, effective 11/5/2019.