Ariz. Admin. Code § tit. 3, ch. 7, art. 10, tbl. 1

Current through Register Vol. 30, No. 50, December 13, 2024
Table 1 - Acceptability of Final System Pressure Results for Systems Tested Using TP-201.3

Ullage (gallons)

Minimum Pressure after Five Minutes (Inches Water Column)

500

0.73

550

0.80

600

0.87

650

0.93

700

0.98

750

1.03

800

1.07

850

1.11

900

1.15

950

1.18

1000

1.21

1200

1.32

1400

1.40

1600

1.46

1800

1.51

2000

1.56

2400

1.62

2600

1.65

2800

1.67

3000

1.69

3500

1.73

4000

1.76

4500

1.79

5000

1.81

6000

1.84

7000

1.86

8000

1.88

9000

1.89

10000

1.90

15000

1.93

20000

1.95

25000

1.96

Ariz. Admin. Code tit. 3, ch. 7, art. 10, tbl. 1

Article 10, New Table 1 recodified from 20 A.A.C. 2, Article 10, Table 1 at 22 A.A.R. 2786, effective August 15, 2016 (Supp. 16-3).