Ariz. Admin. Code § 20-5-416

Current through Register Vol. 30, No. 49, December 6, 2024
Section R20-5-416 - Maximum Allowable Working Pressure
A. The ASME Code under which a Boiler, Lined Hot Water Heater, or Pressure Vessel was constructed and stamped shall determine the MAWP.
B. If components in the Boiler, or hot water system such as valves, pumps, expansion tanks, storage tanks or piping have a lesser working pressure rating than the Boiler or Lined Hot Water Heater, the pressure setting for the Safety Valve Relief Valve, or Safety Relief Valve on the Boiler or Lined Hot Water Heater shall be based upon the component with the lowest MAWP rating.

Ariz. Admin. Code § R20-5-416

Repealed effective April 12, 1979 (Supp. 79-2). New Section adopted effective April 9, 1992 (Supp. 92-2). R20-5-416recodified from R4-13-416 (Supp. 95-1). Amended effective October 9, 1998 (Supp. 98-4). Amended by final rulemaking at 15 A.A.R. 1496, effective August 18, 2009 (Supp. 09-3). Amended by final rulemaking at 28 A.A.R. 3952, effective 12/7/2022.