Energy Efficiency Program for Certain Commercial and Industrial Equipment: Test Procedures and Efficiency Standards for Commercial Air Conditioners and Heat Pumps

Download PDF
Federal RegisterOct 24, 2000
65 Fed. Reg. 63677 (Oct. 24, 2000)

Correction

In proposed rule document 00-19723 beginning on page 48828 in the issue of Wednesday, August 9, 2000, make the following correction:

§431.271
[Corrected]

On page 48837 and 48838, in §431.271, Tables 1 and 2 should read as follows:

TABLE 1.—Minimum Cooling Efficiency Levels

Product Category Cooling capacity Subcategory Efficiency Level
Small Commercial Packaged Air Conditioning and Heating Equipment Air Cooled, 3 Phase <65,000 Btu/h Split System Single Package SEER = 10.0 SEER = 9.7
Air Cooled ≥65,000 Btu/h and <135,000 Btu/h All EER = 8.9
Water Cooled Evaporatively Cooled, and Water-Source <65,000 Btu/h ≥65,000 Btu/h and <135,000 Btu/h All All EER = 9.3 EER = 10.5
Large Commercial Packaged Air Conditioning and Heating Equipment Air Cooled ≥135,000 Btu/h and <240,000 Btu/h All EER = 8.5
Water-Cooled, and Evaporatively Cooled ≥135,000 Btu/h and <240,000 Btu/h All EER = 9.6
Packaged Terminal Air Conditioners and Heat Pumps All <7,000 Btu/h ≥7,000 Btu/h and ≤15,000 Btu/h >15,000 Btu/h All EER = 8.88 EER = 10.0−(0.16 × capacity [in thousands of Btu/h at 95° outdoor dry-bulb temperature]) EER = 7.6
All EER values must be rated at 95°F outdoor dry-bulb temperature for air-cooled products and evaporatively-cooled products and at 85°F entering water temperature for water-source and water-cooled products.

TABLE 2.—MINIMUM HEATING EFFICIENCY LEVELS

Product Category Cooling capacity Subcategory Efficiency Level
Small Commercial Packaged Air Conditioning and Heating Equipment Air Cooled, 3 Phase <65,000 Btu/h Split System Single Package HSPF = 6.8 HSPF = 6.6
Water-Source <135,000 Btu/h Split System and Single Package COP = 3.8
Air Cooled ≥65,000 Btu/h and <135,000 Btu/h All COP = 3.0
Large Commercial Packaged Air Conditioning and Heating Equipment Air Cooled ≥135,000 Btu/h and <240,000 Btu/h Split System and Single Package COP = 2.9
Packaged Terminal Heat Pumps All All All COP = 1.3+(0.16 × the applicable minimum cooling EER prescribed in Table 1—Minimum Cooling Efficiency Levels)
All COP values must be rated at 47°F outdoor dry-bulb temperature for air-cooled products and evaporatively-cooled products and at 70°F entering water temperature for water-source products.

Correction

In rule document 00-25599 beginning on page 60101 in the issue of Tuesday, October 10, 2000, make the following corrections:

§52.1770
[Corrected]

1. On page 60102, in §52.1770 (c), in the table, in the section “Subchapter 2D—Air Pollution Control Requirements”, in the first line, the column for “State effective date” should read “1/15/98” and the column for “EPA approval date” should read “11/10/99”.

2. On page 60103, in the same section of the table, in the last line, in the column for “State effective date”, “Annual Emissions Reporting” should read “1/15/98”. The column for “EPA approval date” should read “11/10/99” and the column for “Comments” should read “*”.

Correction

In notice document 00-25579 beginning on page 59463, in the issue of Thursday, October 5, 2000, make the following correction:

On page 59463, in the third column, in the seventh line from the bottom, “ Sec. 3, SE 1/4 NW 1/2” should read “ Sec. 3, SE 1/4 NW 1/4 ”.

[FR Doc. C0-19723 Filed 10-23-00; 8:45 am]

BILLING CODE 1505-01-D

[FR Doc. C0-25599 Filed 10-23-00; 8:45 am]

BILLING CODE 1505-01-D

[FR Doc. C0-25579 Filed 10-23-00; 8:45 am]

BILLING CODE 1505-01-D