Energy Conservation Program: Energy Conservation Standards for Uninterruptible Power Supplies

Download PDF
Federal RegisterJan 21, 2020
85 Fed. Reg. 3232 (Jan. 21, 2020)

Correction

In rule document 2019-2635 beginning on page 1447 in the issue of Friday, January 10, 2020, make the following correction:

§ 430.32
[Corrected]

On page 1503, in § 430.32(z)(3) the table should appear as follows:

Battery charger product class Rated output power Minimum efficiency
10a (VFD UPSs) 0 W < P rated ≤ 300 W −1.20E-06 * P rated + 7.17E-04 * P rated + 0.862.
300 W < P rated ≤ 700 W −7.85E-08 * P rated + 1.01E-04 * P rated + 0.946.
P rated > 700 W −7.23E-09 * P rated + 7.52E-06 * P rated + 0.977.
10b (VI UPSs) 0 W < P rated ≤ 300 W −1.20E-06 * P rated + 7.19E-04 * P rated + 0.863.
300 W < P rated ≤ 700 W −7.67E-08 * P rated + 1.05E-04 * P rated + 0.947.
P rated > 700 W −4.62E-09 * P rated + 8.54E-06 * P rated + 0.979.
10c (VFI UPSs) 0 W < P rated ≤ 300 W −3.13E-06 * P rated + 1.96E-03 * P rated + 0.543.
300 W < P rated ≤ 700 W −2.60E-07 * P rated + 3.65E-04 * P rated + 0.764.
P rated > 700 W −1.70E-08 * P rated + 3.85E-05 * P rated + 0.876.

[FR Doc. C1-2019-26354 Filed 1-17-20; 8:45 am]

BILLING CODE 1301-00-D