Rohlik, Michael Lawrence. et al.Download PDFPatent Trials and Appeals BoardNov 12, 20202019002047 (P.T.A.B. Nov. 12, 2020) Copy Citation UNITED STATES PATENT AND TRADEMARK OFFICE UNITED STATES DEPARTMENT OF COMMERCE United States Patent and Trademark Office Address: COMMISSIONER FOR PATENTS P.O. Box 1450 Alexandria, Virginia 22313-1450 www.uspto.gov APPLICATION NO. FILING DATE FIRST NAMED INVENTOR ATTORNEY DOCKET NO. CONFIRMATION NO. 14/312,299 06/23/2014 Michael Lawrence Rohlik M74811 1010US.1 (0002.4) 8612 26158 7590 11/12/2020 WOMBLE BOND DICKINSON (US) LLP ATTN: IP DOCKETING P.O. BOX 7037 ATLANTA, GA 30357-0037 EXAMINER BARRERA, JUAN C ART UNIT PAPER NUMBER 3752 NOTIFICATION DATE DELIVERY MODE 11/12/2020 ELECTRONIC Please find below and/or attached an Office communication concerning this application or proceeding. The time period for reply, if any, is set in the attached communication. Notice of the Office communication was sent electronically on above-indicated "Notification Date" to the following e-mail address(es): BostonDocket@wbd-us.com IPDocketing@wbd-us.com PTOL-90A (Rev. 04/07) UNITED STATES PATENT AND TRADEMARK OFFICE BEFORE THE PATENT TRIAL AND APPEAL BOARD Ex parte MICHAEL LAWRENCE ROHLIK, KENNETH ALAN HUBBARD, and JOHN EMMETT BEVINS Appeal 2019-002047 Application 14/312,299 Technology Center 3700 Before DANIEL S. SONG, JILL D. HILL, and JEREMY M. PLENZLER, Administrative Patent Judges. HILL, Administrative Patent Judge. DECISION ON APPEAL STATEMENT OF THE CASE Pursuant to 35 U.S.C. § 134(a), Appellant1 appeals from the Examiner’s decision to reject claims 1–8, 12–15, 17, and 24–292. We have jurisdiction under 35 U.S.C. § 6(b). We AFFIRM. 1 We use the word Appellant to refer to “applicant” as defined in 37 C.F.R. § 1.42. Appellant identifies the real party in interest as McWane, Inc. Appeal Br. 1. 2 Claims 18–23 were withdrawn from consideration. Claims 9–11 and 16 were canceled. Final Act. 2. Appeal 2019-002047 Application 14/312,299 2 BACKGROUND Independent claims 1 (method) and 12 (system) are pending and not withdrawn. Independent claim 1, reproduced below, illustrates the claimed invention. 1. A method for testing a vehicle fire suppression system, the method comprising: testing, via processing circuitry, each of a plurality of components of the vehicle fire suppression system; and providing test results for each of the plurality of components, wherein the plurality of components comprises one or more status indicator lights, a shutdown relay configured to disable vehicle operation in event of a fire, a power supply system, at least one fire detection sensor, an audible alarm, and an extinguishing agent container, and wherein testing each of the plurality of components of the vehicle fire suppression system includes: testing operation of each of the one or more status indicator lights; engaging the shutdown relay; testing the power supply system; testing the at least one fire detection sensor; triggering the audible alarm; and testing pressurization of the extinguishing agent container. REFERENCES The prior art relied upon by the Examiner is: Name Reference Date Lloyd US 5,950,150 Sept. 7, 1999 Rini US 2010/0320021 A1 Dec. 23, 2010 Turaev US 2013/0299203 A1 Nov. 14, 2013 Appeal 2019-002047 Application 14/312,299 3 REJECTION Claims 1–8, 12–15, 17, and 24–29 stand rejected under 35 U.S.C. § 103 as unpatentable over Turaev, Lloyd, and Rini. Final Act. 2. OPINION The Examiner finds, inter alia, that Turaev discloses a vehicle suppression system, but not a method for testing components of the vehicle suppression system. Final Act. 2–3. The Examiner finds, however, that Lloyd discloses a method for testing a vehicle suppression system that includes testing each component of a fire suppression system having sensors, and providing test results for each of the components. Id. at 3 (citing Lloyd 11:25–29 (“the on-site portion 10 consists of one or more sensors that sense one or more parameters of one or more components of a fire protection system pertinent to operational criteria compliance verification”); 13:3–10 (data is recorded and tested)). The Examiner also finds that Lloyd discloses the tested suppression system components including status indicator lights (control panel indicia), a power supply system (driver 48), a fire detection sensor (sensing one or more parameters like temperature, fire or smoke), an audible alarm, and an extinguishing agent container (water tanks). Id. (citing Lloyd 5:20–31, 8:8–24, 14:39–48, 16:63–17:4). The Examiner continues that Lloyd further discloses testing each of the plurality of components, including testing operation of status indicator lights, testing the power supply system, testing detection sensors, triggering the audible alarm, and testing pressurization of the extinguishing agent container. Id. at 3–4. The Examiner concludes that it would have been obvious to modify Turaev to incorporate Lloyd’s testing method to provide Turaev’s “vehicle fire suppression system with a method to test, diagnose and provide results . . . to Appeal 2019-002047 Application 14/312,299 4 automatically verify operational criteria to inform the user of the status of the system (see abstract).” Id. at 4. Appellant argues claims 1–8, 12–15, 17, and 24–29 as a group. Appeal Br. 6. We select independent method claim 1 as representative. Claims 2–8, 12–15, 17, and 24–29 stand or fall with claim 1. See 37 C.F.R. § 41.37(c)(1)(iv). Appellant argues that the Examiner erred in finding that Lloyd discloses processing circuitry triggering an audible alarm and testing the status indicator light(s), a power supply system, and fire detection sensors. Appeal Br. 4. According to Appellant, while Lloyd discloses verifying compliance of a fire/life safety system by sensing various system parameters “during testing to determine if testing requirements are satisfied,” Lloyd “does not itself test components of the fire/life safety system” or explicitly “disclose that its system senses parameters during testing of each of indicator light(s), power supply system or fire detection sensor(s), or triggers an audible alarm.” Id. (emphasis omitted). Appellant addresses and summarizes each section of Lloyd’s text cited by the Examiner, explaining how each section fails to disclose testing the claimed components of Lloyd’s fire suppression system. Id. at 4–6. The Examiner responds that Lloyd’s sensing of parameters to verify system compliance with safety codes “requires testing of the components claimed by Appellant.” Ans. 12. According to the Examiner, the operation, maintenance, and testing of Lloyd’s fire suppression system components are “established by predetermined operational criteria, such as industry standards and fire safety codes,” such that the compliance verification disclosed in Lloyd includes testing of fire suppression system components Appeal 2019-002047 Application 14/312,299 5 when required. Id. at 13. Regarding testing of fire detection sensors specifically, the Examiner finds that “[L]loyd is testing the sensors by sensing them for operational criteria.” Id. Regarding testing by triggering the audible alarm and testing status indicator lights, the Examiner finds that Lloyd’s sensor 116 “senses the fire protection system’s alarm device . . . to insure [sic, ensure] that quarterly testing requirements of NFPA . . . [are] performed on schedule.” Ans. 13–14. The Examiner contends that NFPA requires testing of fire alarms for visual and audible features, such that Lloyd’s sensor 116 would be understood by a skilled artisan to test the visual and audible alarm features. Id. Regarding testing the power supply system specifically, the Examiner finds that “[t]he claims do not specify what kind of power supply,” and Lloyd’s diesel driven pump is a power supply that is tested by its “exhaust thermocouple 54 sens[ing] the operational status of the pump.” Id. at 14. Appellant replies that, while Lloyd senses parameters during testing to determine if testing requirements are satisfied, Lloyd “does not itself test components of the fire/life safety system[,] . . . [n]or does Lloyd specifically disclose that its system senses parameters during testing of each of indicator light(s), power supply system or fire detection sensor(s), or triggers an audible alarm.” Reply Br. 2. According to Appellant, while Lloyd discloses a “system for operational criteria compliance of fire/life safety systems and components,” it does not “mention operational status or testing operational status of components of a fire safety system, much less that its system tests operational status for components of a fire safety system.” Id. Appellant again addresses and summarizes each section of text cited by the Examiner, explaining how each section fails to disclose testing the claimed components Appeal 2019-002047 Application 14/312,299 6 of the fire suppression system. Id. at 2–5. Regarding the Examiner’s assertion that Lloyd’s sensor 116 “senses the fire protection system’s alarm device . . . to insure that quarterly testing requirements of NFPA . . . [are] performed on schedule,” and NFPA requires testing of fire alarms for visual and audible features (Ans. 13–14), Appellant argues that “Lloyd does not disclose or describe NFPA 72 Chapter 14, nor is NFPA 72 Chapter 14 of record or cited” in the pending rejection. Reply Br. 5 (emphasis omitted). We are not persuaded that the Examiner’s findings regarding the disclosure of Lloyd contain error. Lloyd discloses a method for verifying operational criteria compliance for components of a fire/life safety system whose testing is established by predetermined operational criteria. Lloyd, Abstract. Sensors sense parameters of, or resultant indicators of, one or more of the fire/life safety system components to verify compliance thereof. See id. According to Lloyd, the National Fire Protection Association (NFPA) developed industry standards for, inter alia, testing fire protection systems. Lloyd 2:3–8. NFPA Standard 25 regulates such testing and includes, inter alia, testing the pump and the alarm device. See id. at 2:19– 52. Lloyd discloses that fire detection/alarm system test requirements “are as diverse as the systems themselves,” and “vary depending on system configuration.” Lloyd 6:5–9, 50–53. Lloyd “pulls together each [fire/life safety system’s] operational requirements into an integrated fire/life safety operational criteria compliance . . . method that can verify the state of readiness of the entire fire/life safety system, as well as the degree of its code compliance.” Id. at 9:6–11. Such operation criteria compliance includes fire/life safety system components whose testing is established by Appeal 2019-002047 Application 14/312,299 7 industry standards and codes. Id. at 10:64–11:2. A portion 10 of the system includes sensors (see, e.g., the sensors listed at 15:14–23 and 16:3–13) that sense parameters of the components pertinent to operational criteria compliance. Id. at 11:26–29. For example, an exhaust thermocouple 54 senses heat from a diesel exhaust stack 52 to verify the operation of diesel driver 48. Id. at 14:22–26. In addition, sensors 80, 82 detect battery current or voltage “indicative of whether batteries 70 and 72 have enough remaining capacity to start the diesel driver 48.” Id. at 14:64–67. According to Lloyd, its sensors “provide information necessary to determine the existence of problem conditions . . . . Examples of these are sensors 80 and 82, which may indicate that both the main battery and reserve battery sets have insufficient remaining voltage to provide start up of the diesel driver.” Id. at 15:59–67. Lloyd also includes a sensor 116 that “senses the fire protection system’s alarm device . . . to insure that quarterly testing requirements of NFPA to exercise this device [are] performed on schedule.” Id. at 16:63– 17:1. “[H]eat or smoke sensors 138 are provided in several zones within each floor,” and can be monitored as a “primary method in which the preaction system is tripped. Id. at 18:29–33. Lloyd’s Figures 22, 23, 24, and 25 illustrate an exemplary “fire/life safety operational criteria compliance verification report.” Lloyd 10:32–33. As can be seen, the report indicates that alarm testing (Figure 24) and power testing (Figure 25) was performed. Thus, whether or not Lloyd’s system performs the testing, it discloses such testing, i.e., a method, being performed as part of a fire/life safety testing system. Thus, when considered a whole, Lloyd teaches that fire detection/alarm systems and their various components, including sensors, Appeal 2019-002047 Application 14/312,299 8 are employed, tested, and monitored throughout such systems to ensure that any required industry standard or code testing is performed and compliance thereto verified. Thus, the premise of the Appellant’s arguments as to lack of disclosure in Lloyd as to testing is unpersuasive. We agree with the Examiner that it would have been obvious to a skilled artisan to verify operation through testing of the system of Turaev in view of the fire/life safety verification of Lloyd’s method. For these reasons, we discern no error in the Examiner’s rejection, and we sustain the Examiner’s rejection. CONCLUSION We sustain the pending obviousness rejection. DECISION SUMMARY Claims Rejected 35 U.S.C. § Reference(s)/Basis Affirmed Reversed 1–8, 12– 15, 17, 24– 29 103 Turaev, Lloyd, Rini 1–8, 12– 15, 17, 24– 29 TIME PERIOD FOR RESPONSE No time period for taking any subsequent action in connection with this appeal may be extended under 37 C.F.R. § 1.136(a). See 37 C.F.R. § 1.136(a)(1)(iv). AFFIRMED Copy with citationCopy as parenthetical citation