Section 51-11C-40620 - Section C406.2-Additional energy efficiency credit measures
C406.2Additional energy efficiency credit measures. Each energy efficiency credit measure used to meet credit requirements for the project shall include efficiency that is greater than the energy efficiency required for the building type and configuration requirements in Sections C402 through C405. Measures installed in the project that meet the requirements in Sections C406.2.1 through C406.2.14 shall achieve the credits listed for the measure and occupancy group in Table C406.2(1) or Table C406.2(2) or where calculations required by Sections C406.2.1 through C406.2.14 create or modify the table credits, the credits achieved shall be based upon the section calculations. Projects that chose to comply with the fossil fuel pathway in Section C401.3 shall use Table C406.2(2) to achieve credits.

For mixed fuel space heating systems, the number of space heating energy efficiency credits available for measures with a prorating flag "Heat" are calculated using the following equation:

Click here to view image

For mixed fuel service water heating systems, the number of service water heating energy efficiency credits available for measures with a prorating flag "SWH" are calculated using the following equation:

Click here to view image

Click here to view image

Table C406.2(1)

Efficiency Measure Credits

Measure Title

Applicable Section

Prorating Flag

Occupancy Group

Group R-1

Group R-2

Group B

Group E

Group M

All Other

1. Dwelling unit HVAC control

C406.2.1

Heat

NA

7

NA

NA

NA

NA

2. Improved HVAC TSPRa

C406.2.2.1

Heat

NA

8

11

17

22

NA

3. Improve cooling and fan efficiency

C406.2.2.2

Heat

2

2

3

4

3

2

4. Improve heating efficiency

C406.2.2.3

Heat

2

3

3

10

16

7

5. Improved low-carbon district energy system (10% better)

C406.2.2.4

3

3

4

11

17

8

6. Improved low-carbon district energy system (20% better)b

C406.2.2.5

9

10

12

33

52

24

7. High performance DOAS

C406.2.2.6

Heat

31

31

21

39

40

21/

(A) 40c

8. Fault detection &diagnostics (FDD)

C406.2.2.7

Heat

2

2

2

6

9

4

9. 10% reduced lighting power

C406.2.3.1

Heat

7

4

18

16

20

15

10. 20% reduced lighting powerd

C406.2.3.2

Heat

13

8

36

32

40

29

11. Lamp efficacy improvement

C406.2.3.3

Heat

5

6

NA

NA

NA

NA

12. Residential lighting control

C406.2.4.1

Heat

NA

8

NA

NA

NA

NA

13. Enhanced lighting control

C406.2.4.2

Heat

1

1

6

6

11

6

14. Renewable energy

C406.2.5

7

12

13

13

10

11

15. Shower drain heat recovery

C406.2.6.1

SWH

9

30

NA

3

NA

NA

16. Service water heat recovery

C406.2.6.2

SWH

35

111

13

14

(Grocery) 41e

NA

17. Heat pump water heating

C406.2.6.3

SWH

72

54

1

13

5

29f

18. High efficiency service water heating, gas-fired

C406.2.6.4

SWH

NA

NA

NA

NA

NA

NA

19. Heat trace system

C406.2.7.1

SWH

6

13

4

1

NA

6

20. Point of use water heater

C406.2.7.2

SWH

NA

NA

19

5

NA

NA

21. Service hot water distribution right sizing

C406.2.8

13

42

NA

NA

NA

NA

22. High performance service hot water temperature maintenance system

C406.2.9

6

13

4

1

NA

6

23. High efficiency service hot water circulation system

C406.2.10

3

6

2

1

NA

4

24. Low flow residential showerheads

C406.2.11

SWH

3

3

NA

NA

NA

NA

25. Enhanced envelope performanceg

C406.2.12

Heat

24

20

13

5

19

14

26. Base reduced air leakageg

C406.2.13.1

29

24

6

3

9

11

27. Enhanced reduced air leakageg

C406.2.13.2

Heat

53

44

11

5

16

20

28. Enhanced commercial kitchen equipment

C406.2.14

Heat

30h

18h

18h

30h

30h

31h

29. Enhanced residential kitchen equipment

C406.2.15

Heat

12

19

NA

NA

NA

NA

30. Enhanced residential laundry equipment

C406.2.16

Heat

NA

6

NA

NA

NA

NA

31. Heat pump clothes dryers

C406.2.17

Heat

6

6

NA

NA

NA

NA

32. Efficient elevator equipment

C406.2.18

Heat

3

5

5

5

4

4

a Projects using Item 2 shall not use Items 3, 4, or 7.

b Projects using C406.2.2.5 shall not use C406.2.2.4.

c For C406.2.2.6, occupancy Group A achieves 40 credits while other occupancy groups within the "all other" category achieve 21 credits.

d Projects using C406.2.3.2 shall not use C406.2.3.1.

e Service water heat recovery and heat pump water heating are available in Group M only for grocery stores larger than 10,000 ft2. Large mixed retail with full grocery and butcher sections shall achieve half the credits. This credit is not available where refrigeration recovery to heat service hot water is used to meet the requirements of Section C403.9.2.3.

f Heat pump water heating efficiency credits are available in the "all other" category only for Group A-2.

g Buildings or building areas that are exempt from the thermal envelope requirements in accordance with Sections C402.1.1 and C402.1.2, do not qualify for this package.

h Additional energy efficiency credits, up to the maximum shown in Table C406.2(1), shall be calculated according to Section C406.2.14.

Table C406.2(2)

Efficiency Measure Credits for use with Fossil Fuel Compliance Path

Measure Title

Applicable Section

Prorating Flag

Occupancy Group

Group R-1

Group R-2

Group B

Group E

Group M

All Other

1. Dwelling unit HVAC control

C406.2.1

Heat

NA

8

NA

NA

NA

NA

2. Improved HVAC TSPRa

C406.2.2.1

Heat

NA

9

12

19

24

NA

3. Improve cooling and fan efficiency

C406.2.2.2

Heat

12

8

14

8

10

10

4. Improve heating efficiency

C406.2.2.3

Heat

2

3

3

11

18

8

5. Improved low-carbon district energy system (10% better)

C406.2.2.4

3

3

4

12

19

9

6. Improved low-carbon district energy system (20% better)b

C406.2.2.5

10

11

13

36

57

26

7. High performance DOAS

C406.2.2.6

Heat

34

34

23

43

44

23/

(A) 40c

8. Fault detection & diagnostics (FDD)

C406.2.2.7

Heat

2

2

2

6

9

4

9. 10% reduced lighting power

C406.2.3.1

Heat

7

4

18

16

20

15

10. 20% reduced lighting powerd

C406.2.3.2

Heat

13

8

36

32

40

29

11. Lamp efficacy improvement

C406.2.3.3

Heat

5

6

NA

NA

NA

NA

12. Residential lighting control

C406.2.4.1

Heat

NA

8

NA

NA

NA

NA

13. Enhanced lighting control

C406.2.4.2

Heat

1

1

6

6

11

6

14. Renewable energy

C406.2.5

7

12

13

13

10

11

15. Shower drain heat recovery

C406.2.6.1

SWH

10

33

NA

3

NA

NA

16. Service water heat recovery

C406.2.6.2

SWH

35

111

13

14

(Grocery) 41e

NA

17. Heat pump water heating

C406.2.6.3

SWH

135

163

17

33

(Grocery) 95e

(A-2) 95f

18. High efficiency service water heating, gas-fired

C406.2.6.4

SWH

59

65

6

11

18

32

19. Heat trace system

C406.2.7.1

SWH

6

13

4

1

NA

6

20. Point of use water heater

C406.2.7.2

SWH

NA

NA

19

5

NA

NA

21. Service hot water distribution right sizing

C406.2.8

13

42

NA

NA

NA

NA

22. High performance service hot water temperature maintenance system

C406.2.9

6

13

4

1

NA

6

23. High efficiency service hot water circulation system

C406.2.10

3

6

2

1

NA

4

24. Low flow residential showerheads

C406.2.11

SWH

3

3

NA

NA

NA

NA

25. Enhanced envelope performanceg

C406.2.12

Heat

24

20

13

5

19

14

26. Base reduced air leakageg

C406.2.13.1

29

24

6

3

9

11

27. Enhanced reduced air leakageg

C406.2.13.2

Heat

53

44

11

5

16

20

28. Enhanced commercial kitchen equipment

C406.2.14

Heat

30h

18h

18h

30h

30h

31h

29. Enhanced residential kitchen equipment

C406.2.15

Heat

12

19

NA

NA

NA

NA

30. Enhanced residential laundry equipment

C406.2.16

Heat

NA

6

NA

NA

NA

NA

31. Heat pump clothes dryers

C406.2.17

Heat

6

6

NA

NA

NA

NA

32. Efficient elevator equipment

C406.2.18

Heat

3

5

5

5

4

4

a Projects using Item 2 shall not use Items 3, 4, or 7.

b Projects using C406.2.2.5 shall not use C406.2.2.4.

c For C406.2.2.6, occupancy Group A achieves 40 credits while other occupancy groups within the "all other" category achieve 21 credits.

d Projects using C406.2.3.2 shall not use C406.2.3.1.

e Service water heat recovery and heat pump water heating are available in Group M only for grocery stores larger than 10,000 ft2. Large mixed retail with full grocery and butcher sections shall achieve half the credits. This credit is not available where refrigeration recovery to heat service hot water is used to meet the requirements of Section C403.9.2.3.

f Heat pump water heating efficiency credits are available in the "all other" category only for Group A-2.

g Buildings or building areas that are exempt from the thermal envelope requirements in accordance with Sections C402.1.1 and C402.1.2, do not qualify for this package.

h Additional energy efficiency credits, up to the maximum shown in Table C406.2(2), shall be calculated according to Section C406.2.14.

Wash. Admin. Code § 51-11C-40620

Adopted by WSR 22-14-091, Filed 7/1/2022, effective 7/1/2023
Amended by WSR 24-03-085, Filed 1/16/2024, effective 3/15/2024
Amended by WSR 24-16-145, Filed 8/7/2024, effective 9/7/2024