N.Y. Comp. Codes R. & Regs. tit. 12 § 14-1.13

Current through Register Vol. 46, No. 16, April 17, 2024
Section 14-1.13 - Boiler operator
(a) Every person attending a boiler shall be provided sufficient training to allow that person sufficient knowledge to operate the boiler in a safe and efficient manner.
(b) The boiler operator shall keep a log for each shift that he is responsible for operating the boiler. That log shall provide the following information, which may vary according to type of boiler:
(1) blowdown of water column and sight glass and other safety equipment;
(2) blowdown of mud drum and headers;
(3) record of water treatment;
(4) test of safety valves;
(5) record of any operating problems or deficiencies; and
(6) signature of boiler operator.
(c) The log shall be available for inspection by the State boiler inspector and the insurance carrier inspector.

N.Y. Comp. Codes R. & Regs. Tit. 12 § 14-1.13