N.H. Admin. Code § Saf-C 3306.03

Current through Register No. 45, November 7, 2024
Section Saf-C 3306.03 - Construction Details

Documents for modular buildings and building components shall include the following:

(a) Typical details, including:
(1) Methods of installation of modular buildings or building components on foundations or to each other;
(2) Floor plan(s) and elevation(s);
(3) Cross sections specific to the building system necessary to identify major building components;
(4) Details of flashing including material or gauge at openings and penetrations through roofs and subcomponent connections, including weather barriers and roof system underlayment;
(5) Attic access and attic ventilation, if required by code;
(6) Exterior wall, roof, and soffit material;
(7) Interior wall and ceiling material;
(8) Barrier free provisions, if applicable;
(9) Sizes, locations, and types of doors and windows;
(10) Foundation dimensional plans; and
(11) Insulation values and materials;
(b) Fire safety details, including:
(1) Details and locations of fire rated assemblies, including reference listing or test report for all:
a. Stairway enclosures;
b. Doors;
c. Walls;
d. Floors;
e. Ceilings;
f. Partitions;
g. Columns;
h. Roof; and
i. Other enclosures;
(2) Details of means of egress, including:
a. Aisles;
b. Exits;
c. Corridors;
d. Passageways;
e. Stairway enclosures; and
f. Handrails and guardrails;
(3) Flame spread and smoke development classification of interior finish materials;
(4) Location of required draftstops, fireblocking, and through-penetration fire-rated assemblies;
(5) Opening protectives in fire resistance rated systems and assemblies; and
(6) Drawings and calculations of fire suppression systems, standpipes, fire alarms, and detection systems, if required;
(c) Structural details, including:
(1) Calculations of structural members and test results, except when compliance can be demonstrated through code tables, product manufacturer handbooks, and listing document;
(2) Details of structural elements, including framing, spacing, size, and connections;
(3) Grade, type, and specifications of materials;
(4) Schedule of roof, floor, wind, and seismic loads on which design is based;
(5) Column loads and column schedule; and
(6) Design and calculations of high-wind connections, including required foundation load, as applicable;
(d) Mechanical details, including:
(1) Location of all equipment, appliances, and baseboard radiation units;
(2) Equipment and appliance listing and labeling agencies;
(3) Energy conservation calculations, using rescheck, as defined in Saf-C 3302.24;
(4) Make, model number, and input/output rating of all equipment and appliances;
(5) Duct and register locations, sizes, and materials;
(6) Method of providing combustion air, if required; and
(7) Location of flues, vents, and chimneys, clearances from air intakes, combustible materials, and other vents and flues;
(e) Plumbing details, including:
(1) Schematic drawing of the:
a. Plumbing layout, including the size of piping, fittings, traps, and vents;
b. Cleanouts and valves; and
c. Gas, water, and drainage systems; and
(2) Plumbing materials, including:
a. Location of all equipment, appliances, and safety controls to be used;
b. Make, model, rating, and capacity of equipment and appliances; and
c. Equipment and appliance listing or labeling agencies; and
(f) Electrical details, including:
(1) Service equipment;
(2) Method of grounding service equipment;
(3) Load calculations for service and feeders;
(4) Sizes of branch circuit conductors;
(5) Size, rating and location of main disconnect and over current protective devices; and
(6) Location of outlets, junction boxes, fixtures and appliances.

N.H. Admin. Code § Saf-C 3306.03

#5439, eff 7-24-92; ss by #6810, INTERIM, eff 7-25-98, EXPIRES: 11-22-98; ss by #6885, eff 11-18-98;ss by #8741, INTERIM, eff 11-18-06, EXPIRED: 5-17-07

New. #9752, eff 7-9-10 (from Saf-C 3307.03)

Amended by Volume XXXIX Number 16, Filed April 18, 2019, Proposed by #12737, Effective 3/8/2019, Expires 3/8/2029.